Ethernet/IP™ Klassen SAI-AU
8.10 Class 0B
: Analog Output Point Object
H
Dieses Objekt definiert die analogen Ausgänge der SAI Produktreihe.
Klassenattribute
Number
Name
Data Type
Access
Description
Instanzattribute für Instance 1..X
Number
Name
Data Type
Access
Description
Value:
Number
Name
Data Type
Access
Description
Output Range:
80
1
Revision
Unsigned Integer UINT
Get
Revision of the Analog Output Point Object Class Definition.
3
Value
Unsigned Integer UINT
Get/Set
Analog Output Point Value
0..4095
-10 V to 10 V
0..2047
0 V to 10 V
0..4095
0 mA to 20 mA
819..4095
4 mA to 20 mA
7
Output Range
Unsigned Short Integer USINT
Get/Set
Output Range the Point is operating in
0
4 mA to 20 mA
1
0 V to 10 V
2
0 mA to 20 mA
3
-10 V to 10 V
1.1/03.10