Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy Phoenix 12/3000 Anleitung Seite 15

Vorschau ausblenden Andere Handbücher für Phoenix 12/3000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 65
5.4 Implementing settings with a VE.Net panel
To this end, a VE.Net panel and the VE.Net to VE.Bus converter is required.
With VE.Net you can set all parameters, with the exception of the multi-functional relay
and the VirtualSwitch.
5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position I).
Procedure:
Remarks:
- Dipswitches ds8,ds7 and ds6 are not assigned and should remain off.
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost
DIP switch has the highest number (8), descriptions start with the switch numbered 5.
- In parallel mode or 3-phase mode, not all devices require all settings to be made
(see section 5.5.4).
- For parallel or 3-phase mode, read the whole setting procedure and make a note of
the required DIP switch settings before actually implementing them.
- The 'down' button is not used in this procedure and must not be pressed!
Note:
This manual is intended for inverters with firmware number xxxx1xx (with x any
number).
Downloaded from
www.Manualslib.com
Turn the Inverter on, preferably unloaded.
Set the DIP switches for:
AES (Automatic Economy Switch)
o
Inverter voltage
o
Inverter frequency
o
selection of stand-alone, parallel or 3-phase operation.
o
To store the settings after the required values have been set: press the 'Up'
button for 2 seconds (upper button to the right of the DIP switches, see
appendix A, position J).
manuals search engine
13

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis