6.1 GETTING STARTED

Read item 5 USAGE CONDITIONS

6.2 SHAFT CONECTION TO POWER UNIT

Power unit is designed to facilitate a quick and safe connection to flexible shaft.
CONNECTION PROCEDURE:
CONNECTION CHOICES :

6.3 ELECTRIC MOTOR CONECTION TO THE SYSTEM

6.4 EARTH CONNECTION

en

6.5 EXTENSION CABLES

6.6 PROCEDURE TO DETERMINE THE NECESSARY TRANSVERSAL SECTION IN
CABLE EXTENSION
AX25, AX38, AX48, AX58
6
TAX1m, TAX1-5m, TAX2m, TAX3m, TAX4m, TAX5m - AVMU
Downloaded from
www.Manualslib.com

OPERATION AND MAINTENANCE

1. Introduce power unit hexagonal axle into the provided shaft housing
2. Screw plastic nut of shaft to aluminium thread of power unit . (Be aware of nut turns left and not
tool is required)
FLEXIBLE SHAFT LENGTH:
VIBRATOR DIAMETER
:
Turn off the motor switch before connecting it.
To protect the user from an electrical shock, the motor should be correctly connected to earth.
The AVMU motors are equipped with three cables and their respective plugs. The adequate earth
box should be used to connect the motors. If the boxes are not available, an earth adaptor should be
used, before connecting the plugs.
Always use extension cables with earth wire and its respective plug with earth in the female and
male switches, those which will use the male switch on the motor.
Do not use damaged or worn out cables.
To avoid heavy loads on top of cables.
To determine the transversal section, follow the following procedure
To do the following verifications and take the highest section of cable:
1. The ohmic resistance and inductive cable with the permitted voltage of 5%, cosphi=0,8 trough the
frequency and voltage curve
I.e:
Entering the curve with the product: Intensity x Length=10x100=1000 Am We obtain a 4 mm section
2. The permitted heating of the cable according to VDE ( minimum transversal section table
required).
I. e. For 10 A, according to table for 15 A or inferior, the section is of 1 mm.
Therefore, the section chosen = 4mm, Always chose the highest transversal section of the two
verifications
manuals search engine
TO 5 MTS (TAX 1,5M, TAX3M, TAX 4M AND TAX5M)
TO 58 MM DIAMETER (AX25, AX38, AX48 AND AX58)
Voltage nominal:......... 1- 220 V 50 Hz
Nominal intensity:....... 10 A
Cable length:............... 100 m
AVMU MOTOR - FLEXIBLE SHAFT AND POKERS