Herunterladen Inhalt Inhalt Diese Seite drucken

Wiring Diagram For Modbus - Maico WR 310 Serie Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

UK | 19 Wiring diagram for ModBus – circuit board A2 –

19 Wiring diagram for ModBus

– circuit board A2 –
A
Ventilation unit
A1
Electronic slide-in module
A2
CDV unit control
W11 Connecting cable for ModBus
(provided by customer), e.g.
LIYY 3 x 0.25 mm²
ModBus mode RTU
Baud rate
9600/19200
Data bits
8
Parity
Even
Stop bits
1
Address
10 (basic setting)
62
A
A1
A2
GND
W11
B
A
If the comfort control unit is deactivated in the
parameter menu (touchscreen control unit
RLS T1 WS), the connection terminals on the
RS 485 terminal block can be used as the
ModBus interface. The controlled domestic
ventilation unit can thereby be incorporated
into a building control technology.

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis