European reference standards on safety. It
is classified as follows:
o according to its manufacture: as an
automatic electronic control device to be
incorporated by independent mounting;
o according to its automatic operating fea-
tures: as a 1 B-type operated control type;
o as a Class A device in relation to the cat-
egory and structure of the software.
USE NOT PERMITTED
Any other use other than that permitted is
de facto prohibited. It should be noted
that the relay contacts provided are of a
practical type and therefore subject to
fault. Any protection devices required by
product standards or dictated by common
sense due to obvious safety reasons should
be applied externally.
LIABILITY AND RESIDUAL
RISKS
Invensys Controls Italy S.r.L. shall not be
liable for any damages deriving from:
- installation/use other than that pre-
scribed and, in particular, that which does
not comply with safety standards anticipat-
ed by regulations and/or those given here-
in;
- use on boards which do not guarantee
adequate protection against electric shock,
water or dust under the conditions of
assembly applied;
- use on boards which allow access to dan-
gerous parts without the use of tools;
- tampering with and/or alteration of the
products;
- installation/use on boards not complying
with the standards and provisions of cur-
rent legislation.
DISCLAIMER
This publication is the exclusive property
of Invensys Controls Italy S.r.L. who
absolutely prohibits its reproduction and
distribution unless expressly authorised by
Invensys Controls Italy S.r.L.
Although great care has been taken with
regard to the preparation of this docu-
ment, Invensys Controls Italy S.r.L. does
not assume any responsibility whatsoever
in relation to its use.
Invensys Controls Italy s.r.l
via dell'Industria, 15 Zona Industriale Paludi
32010 Pieve d'Alpago (BL) ITALY
Telephone +39 0437 986111
Facsimile +39 0437 989066
Internet http:/www.climate-eu.invensys.com
11/2001 ing
cod. 9IS22033
ID 961
Tab. 1
Parameter description table
PARAMETER
DESCRIPTION
COMPRESSOR REGULATOR (folder with "CP")
diF
Relay compressor tripping differential. The compressor stops on reaching the Setpoint value (as
indicated by the adjustment probe), and restarts at temperature value equal to the Setpoint plus
the value of the differential.
Note: the value 0 cannot be assumed.
HSE
Maximum possible setpoint value.
LSE
Minimum possible setpoint value.
COMPRESSOR PROTECTIVE DEVICES (folder with "CP" label)
Ont
Compressor activation time in the event of faulty probe. If set to "1" with Oft at "0", the com-
pressor is always on, while for Oft >0, it functions always in duty cycle mode.
OFt
Compressor in disabled state time in the event of a faulty probe. If set to "1" with Ont at "0",
the compressor is always off, while at Ont >0, it functions always in duty cycle mode.
dOn
Delay time in activating the compressor relay after switch-on of instrument.
dOF
Delay after switch off. The indicated time must elapse between switch-off of the compressor
relay and the successive switch-on.
dbi
Delay between switch-ons. The indicated time must elapse between two successive switch-ons of
the compressor.
OdO
delay time in activating the outputs after switch-on of the instrument or after a
power failure.
DEFROSTING REGULATOR (folder with "dEF" label)
dit
Interval between the start of two successive defrosting operations.
dCt
Selection of count mode for the defrosting interval.
0 = compressor operating hours (DIGIFROST® method);
1 = Real Time – appliance operating time;
2 =compressor stop.
dOH
Start-of-defrosting delay time from start up of instrument.
dEt
Defrosting Time out; determines duration of defrosting.
dPO
Request to activate defrosting regulator at switch on. y = yes; n = no.
DISPLAY (folder with label "diS")
LOC
Keyboard locking. However, you can enter parameter programming, modify them and change
the status of this parameter to unlock the keyboard.
y = yes; n = no.
PA1
Password 1. When enabled (value other than 0) it constitutes the access key for level 1 parame-
ters.
CA1
Calibration 1. Positive or negative temperature value added to the value read on the adjustment
room probe (probe 1) before being displayed and used for adjustment.
ddL
Viewing mode during defrosting.
0 = shows the temperature read by the compartment probe;
1 = locks the reading on the temperature value read by the compartment cell when defrosting
starts, and until the next time when Setpoint value is reached;
2 = displays the label "deF" during defrosting and until the next time when Setpoint value is
reached.
dro
Selection of °C or °F to view the temperature read by the probe.
0 = °C, 1 = °F.
CONFIGURATION (folder with label "CnF")
H00
Probe type selection, PTC or NTC. 0 = PTC; 1 = NTC.
rEL
Device version. Read only parameter.
tAb
Reserved. Read only parameter.
COPY CARD (folder with label "Fpr")
UL
UpLoad: transferring parameters from instrument to Copy Card.
downLoad: transferring parameters from Copy Card to instrument.
dL
The same applies to every individual and
company involved in creating and drawing
up this manual. Invensys Controls Italy
S.r.L. reserves the right to make any
amendment, esthetical or functional, with-
out giving prior notice and at any time.

TECHNICAL DATA

Frontal panel protection: IP65.
Container: plastic body in resin type
PC+ABS UL94 V-0, inspection window in
polycarbonate, buttons in thermoplastic
resin.
Dimensions: frontal panel 74x32 mm,
depth 60 mm.
Installation: on panel, with template 71x29
mm (+0.2/–0.1 mm).
Ambient temperature: –5...55 °C.
Storage temperature –30...85 °C.
Operating environment humidity: 10...90%
RH (non condening).
Storage environment humidity: 10...90% RH
(non condensing).
Viewing range: –50...99 °C on 2 digit +
mark display.
Analog inputs: one PTC or NTC input
(selectable through parameter).
Digital outputs: one relay output, SPDT
8(3)A
250Va relay or SPDT 15A(1hp)
250Va relay (for capacity relay see label
on the instrument).
Measuring range: from –50 to 99 °C.
Precision: 0.5% better than full scale.
Resolution: 1 °C.
Consumption: according to model.
Power supply: according to model.
See label on instrument.
2/2