Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens SITRANS Probe LU Kurzanleitung Seite 78

Vorschau ausblenden Andere Handbücher für SITRANS Probe LU:
Inhaltsverzeichnis

Werbung

P211 20 mA Setpoint (high output)
Sets the process level corresponding to the 20 mA value. 20 mA always defaults to 100%,
and P201 determines whether this is a Level, Space, or Distance measurement. Level and
Space are measured as a percentage of Span: Distance is measured as a percentage of
Empty.
Values
Related Parameters
Enter the reading that is to correspond to a 20 mA output, Use percent or units, depending
on the setting for P051
:
Note
P211 is used to set the 20 mA loop current for the HART common module.
mA Output Limit Parameters (P212 and P213)
P212 and P213 allow you to explicitly set a failsafe current outside the normal operating
range.
P212 Minimum mA limit
Prevents the mA output from dropping below this minimum level for a measurement
value. This does not restrict the Failsafe or manual settings.
Values
P213 Maximum mA limit
Prevents the mA output from rising above this maximum level for a measurement value.
This does not restrict the Failsafe or manual settings.
Values
Page 42
SITRANS Probe LU – INSTRUCTION MANUAL
Range
Default
(depends on model)
P201: mA Output Function
.
Range
Default
Range
3.800 to 20.500 (mA)
Default
20.500 (mA)
–99999 to 99999.
5.725 m (18.78 ft) or
11.725 m (38.47 ft); set to 100% as
defined by P201: mA Output Function.
3.800 to 20.500 (mA)
3.800 (mA)
7ML19985HT01

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis