MPORTANT NOTES FOR THE INSTALLER
- Before shutter automation, it is necessary to check the product is in
good condition and that it complies with EN 12604 and the Machines
Directive.
- The control unit is not equipped with a 230 V a/c electric line sec-
tioning device. The installer is responsible for installing a sectioning
device in the system. It is essential to install an overvoltage category
III omnipolar disconnect switch The sectioning device must be posi-
tioned so that it is protected against accidental closure, in compli-
ance with section 5.2.9 of standard EN 12453.
- The wiring of external electrical components must comply with EN
60204-1 as amended in section 5.2.7 of EN 12453. Power supply
leads and connection cables must be secured through the use of
cable clamps, which are supplied with the product.
- As for power cables, we recommend using H05RN-F harmonised
polychloroprene sheathed flexible cables with conductor cross-sec-
tion of at least 0.5mm
2
- The declared IP rating refers to before the intstallation.Take care
when drilling the outer casing to feed through the power and con-
necting cables and when assembling the cable glands, to maintain
the IP degree of protection of the casing as best as possible. Also
take care to fasten the cables firmly in place.
- The back of the casing is set up for mounting on a wall (holes for
mounting with nogs, or holes for screws). Take all precautions to
ensure the IP degree of protection is not affected during installation.
- If applicable, the keypad for manual control must be mounted in
such a way as not to compromise the safety of the user.
- The motor reducer used to move the shutter must comply with sec-
tion 5.2.7. of EN 12453.
- The D.S. Power Supply output is specifically for powering the pho-
tocells. It must not be used for any other applications.
- The control unit tests the working order of the photocells for each
work cycle to guarantee the safety of the Category 2 anti-crushing
devices in accordance with step 5.1.1.6 of EN 12453. The control unit
is disabled whenever the safety devices are not connected and/or not
in good working order.
- For the radio receiver to operate correctly when two more control
units are used, we recommend that you install the devices at least 3
metres away from each other.
The product:
Electronic panel:
LG 2239 - LRS 2239 - LRS 2239 SET - LRH 2239
Complies with the requirements of Directives
RED 2014/53/EU, EMC 2014/30/EU, LVD 2014/35/EU.
Rev. 3.0
13/06/2016
- 10 -