End of battery backup time
All the LEDs go OFF.
The audio alarms stops.
The UPS is completely shut down.

3.3 Return of AC power

Following an outage, the UPS restarts automatically when AC power returns (unless the restart function was disabled
via UPS personalisation) and the load is again supplied.

3.4 UPS shutdown

ESC

3.5 Using the UPS remote control functions

EX has the choice of two remote control options.
RPO: Remote Power Off allows a remote contact to be used to disconnect all the equipment connected to the UPS
from the power supply.
Restarting the UPS requires manual intervention.
ROO: Remote ON/OFF allows remote action of button (27).
These functions are obtained by opening a contact connected between the appropriate pins of connector (5) on the
rear panel of the UPS (see diagram on following page).
34008097EN/AE - Page 16
20
Press button (27) for approximately 2 seconds.
21
22
The devices connected to the UPS are no longer supplied.
27