Battery disposal and safety o Caution. Battery service life is reduced by 50 % for every ten degrees above 25 °C (77 °F). o The battery
must be replaced exclusively by qualified personnel (risk of shock), with new battery approved by Eaton to ensure correct operation of
the UPS. o The battery must be disposed of in accordance with applicable regulations. To remove the battery, shut down the
UPS (button
OFF), remove the power cord and proceed as indicated below "Battery change". o Warning: take care not to inverse the
12
polarity + (red) and - (black) when connecting the battery as this will destroy
the device.
Technical characteristics
Eaton 5S
• UPS power
o Nominal input voltage
o Input frequency
o Voltage/frequency of battery backup
outlets
in battery mode
9
o Total output current for all outlets
o Output current of battery backup
outlets
9
o Input protection
o Transfer time
o Telephone/Data surge protection
o Sealed lead-acid battery
o Average battery life
o Operating temperature
o Storage temperature
o Operating relative humidity
5
550
550 VA / 330
W
50/60 Hz (46 - 70 Hz working range)
230 V +15 % -20 % (50/60 Hz ± 1 Hz)
2.5 A max
12 V, 5 Ah
4 years typical, depending on temperature and number of discharge cycles
700
1000
700 VA / 420
1000 VA / 600
W
W
175 V - 275 V
10 A max
3.2 A max
4.6 A max
10 A resettable circuit breaker
5 ms typical
Tel, ISDN, ADSL, Ethernet
12 V, 7 Ah
2 x 12V, 7 Ah
0 to 35 °C / 32 to 95 °F
-25 °C to +55 °C / -13 °F to 131 °F
0 to 85 %
1500
1500 VA / 900
W
6.8 A max
2 x 12V, 9 Ah
614-06822-00