Basic Operation

Front Panel
ON/OFF Button
1
• To Turn the UPS On: Press and hold the ON/OFF Button for one
second.* If utility power is absent, pressing this button will "cold start"
the UPS by using power from battery.**
• To Turn the UPS Off: Press and hold the ON/OFF Button for one
second.* The UPS will shut off completely.
* The alarm will beep once after one second has passed.
** Providing runtime proportionate to the UPS battery's level of charge.
MUTE/TEST Button
2
• To Silence (or "Mute") UPS Alarms: Briefly press and release the
MUTE/TEST button.
Note: Continuous alarms that warn to shut down connected equipment
immediately cannot be silenced.
• To Run a Self-Test: With the UPS plugged in and turned on, press and
hold the MUTE/TEST button for two seconds. Continue holding the button
until the alarm beeps several times and the UPS performs a self-test
(see Self-Test Results for more information).
Note: Equipment may remain connected during a self-test.
CAUTION! Do not unplug the UPS to test the battery. This will remove safe electrical grounding and may introduce a
damaging surge into network connections.
Results of a Self-Test: The test will last approximately 10 seconds as the UPS switches to battery to test load capacity and charge. All LCD icons
will illuminate and the UPS alarm will sound.
• If the FAULT icon remains illuminated and the alarm continues to sound following the test, the battery-supported outlets are overloaded. To
clear the overload, unplug some equipment from the battery-supported outlets and run the self-test repeatedly until the FAULT icon no longer
illuminates and the alarm no longer sounds.
CAUTION! Any overload not corrected by the user immediately following a self-test may cause the UPS to shut down and
cease supplying output power in the event of a blackout or brownout.
• If the REPLACE icon remains illuminated and the alarm continues to sound following the test, the UPS batteries need recharging or
replacement. Allow the UPS to recharge continuously for 24 hours and repeat the self-test. If the icon continues to illuminate after repeated
self-tests, contact Tripp Lite for service. Battery replacement should only be performed by qualified service personnel. If the UPS requires battery
replacement, visit www.tripplite.com/products/battery-finder/.
LCD Screen
3
The LCD indicates a variety of UPS operational conditions. All descriptions apply when the UPS is plugged into an AC outlet and turned on. The
LCD display may be rotated to match the orientation of the UPS (see Quick Installation for more information).
Input Voltage Meter: This meter measures in real time the AC voltage the UPS system receives from the utility wall outlet. Although the meter
3A
may occasionally display fluctuating input voltages (due to poor utility service) outside the range of standard computer tolerance, the UPS system's
automatic voltage regulation (AVR) feature continuously supplies connected equipment with stable, computer-grade output. In the event of a
blackout (power loss), severe brownout (low power) or overvoltage (high power), the UPS internal battery will supply computer-grade output voltage.
BATTERY CAPACITY Meter: This meter displays the approximate internal battery charge level (in 20% increments). During a blackout or
3B
severe brownout, the UPS will switch to battery power, the ON BAT icon will illuminate and the charge level will deplete.
AVR (Automatic Voltage Regulation) Icon: This icon will illuminate whenever the UPS is automatically correcting low AC line voltage without
3C
depleting battery power. This is a normal operation and no action is required.
REPLACE (Battery Recharge/Replace) Icon: This icon will illuminate and an alarm will sound after a self-test to indicate the UPS
3D
battery needs recharging or replacement. Allow the UPS to recharge continuously for 24 hours and repeat the self-test. If the icon continues to
illuminate, contact Tripp Lite for service. Battery replacement should only be performed by qualified service personnel. If the UPS requires battery
replacement, visit www.tripplite.com/products/battery-finder/.
ON BAT (On Battery) Icon: During a severe brownout or blackout, this icon illuminates and an alarm sounds (four short beeps followed by a
3E
pause) to indicate the UPS is operating from its internal batteries. Monitor the Battery Capacity meter to determine the approximate battery charge
level available. During a prolonged brownout or blackout, the alarm will sound continuously and the BATTERY CAPACITY meter will display one 20%
capacity segment to indicate the batteries are nearly out of power. If this occurs, save files and shut down your equipment immediately.
FAULT Icon: This icon will illuminate and an alarm will sound after a self-test to indicate the battery-supported outlets are overloaded. To clear
3F
the overload, unplug some of the equipment from the battery-supported outlets and run a self-test repeatedly until the icon no longer illuminates
and the alarm no longer sounds.
CAUTION! Any overload not corrected by the user immediately following a self-test may cause the UPS to shut down and
cease supplying output power in the event of a blackout or brownout.
LCD Dimmer: Adjusts the brightness of the LCD screen.
3G
1
ON/OFF Button
2
3
MUTE/TEST
Button
3
3A
3B
3G
3C
3D
3E
LCD Screen
3F