REFRIGERANT PIPING & REFRIGERANT CHARGE
?
N O T E
Hold the cover with a hand to remove screws as the cover may fall down.
Service cover
Hook (three places): two fans
Hook (two places): one fan
a. For the front and side piping
To use racking or conduit tubes, check the size and
remove
part following the slit.
?
N O T E
Place insulation (field supplied) to protect cables and pipes from
being damaged by plate edges.
b. For the downward piping
Liquid piping
?
N O T E
Cables shall not contact directly to the pipes.
c. For the rear side piping
?
N O T E
Remove the rear pipe cover under the rear cover and remove
part following the slit.
10
PMML0397B rev.0 - 11/2015 - P5416650
(picture as example)
Front piping hole
Side piping hole
Cables
Gas piping
Knock-out hole
Bottom base
Rear Cover
2 Mount the piping cover in order to avoid water entering into
the unit. Seal the holes where pipes and wires are inserted,
by using a insulation (field-supplied).
3 If the field-supplied piping is connected with stop valves
directly, it is recommended use a tube bender.
4 Check to ensure that the stop valves are closed completely
before connecting pipes.
5 Connect the field supplied refrigerant pipes to the indoor unit
and outdoor unit. Apply the oil thinly at the seat flare nut and
pipe before tightening.
6 After connecting the refrigerant piping, seal the open space
between knockout hole and refrigerant pipes by using
insulation material.
7 Operation of stop valve should be performed according to
the figure below.

Outdoor unit stop valve
Spindle Type
Closed upon factory shipping
Tightening Torque (Nm)
Liquid valve
7-9
Gas valve
--
Do not apply two
spanners at this
position. If applied,
leakage will occur.
Ball Type
(a)
Spindle valve
Flare nut
Cap
Check joint for service port
49-61
33-42
14-18
100-120
12-14
12-14
Stop valve
(Spindle type)
Flare nut