Herunterladen Inhalt Inhalt Diese Seite drucken

Inhaltsverzeichnis; Installation Location; Unit Installation; Physical Data - McQuay 5WST40AR Montageanleitung

Tandem wasserquellen wärmepumpen split klimaanlage
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 24
- Outline And Dimensions

- Installation Location

- Schematic diagram
- Wiring Diagram
Please take note of the following important points when installing.
• Do not install the unit where leakage of flammable gas may occur.
If gas leaks and accumulates around the unit, it may cause fire ignition.
• Do not overcharge the unit.
This unit is factory pre-charged. Overcharge will cause over-current or damage to the compressor.
This unit is designed for indoor installation only.
Installation work should be done by authorized dealer or qualified contractor.
Install the unit at a suitable minimum distance or shortest path to the coupling fan coil unit.
There should be sufficient space for piping connection, service and maintenance. (Refer to Figure 2)
The area should be isolated from vibration and noise.
Ensure the area is free from water leakage.
This unit will be mounted on the ceiling by the support of four threaded rods. (Refer to Figure 4)
Ensure that the supports are strong enough and properly anchored to withstand the weight of the unit.
Use isolator rubber (natural rubber) with hardness of 35° for better noise and vibration control.
Do not locate the drainage system at any point above the drain connection.
Model
Nominal Cooling Capacity
Nominal Heating Capacity
Unit Weight
Refrigerant Charge R410A
Compressor
Refrigerant Circuit
Liquid valve connection
Gas valve connection
Service port connection (UNF-20)
Refrigerant - Water Heat Exchanger
Water inlet (BSP)MALE
Water outlet (BSP)MALE
Nominal Water pressure drop
Nominal Water flow rate
Drain Pipe Connection
Steel Pipe
INDEX
page i
page i
page v
page vi
page 1
page 1
page 1
page 2
page 2
page 2
page 3
page 3
! CAUTION
INSTALLATION LOCATION

UNIT INSTALLATION

PHYSICAL DATA

1-1
kW
10.84
kW
11.72
kg
105.0
kg
1.925
Rotary Compressor
inches
3/8
inches
5/8
inches
1/2
Tube In Tube
inches
3/4
inches
3/4
12.03
3
m
/h
2.30
inches
3/4
page 3
page 4
page 4
page 4
page 5
page 5
page 5
page 6
page 6
page 7
13.48
15.53
14.65
16.71
134.0
134.0
2.450
3.500
3/8
3/8
5/8
3/4
1/2
1/2
3/4
3/4
3/4
3/4
15.50
22.21
2.90
3.45
3/4
3/4