TAB C COLLEGAMENTI FRIGORIFERI • REFRIGERANT CONNECTION
Mod. CX / CXA
LG
Ø [mm]
CS
[N.m]
LL
Ø [mm]
CS
[N.m]
L max.
[m]
H max.
[m]
LG
= linea gas • gas line
LL
= linea liquido • liquid line
CS
= coppia serraggio raccordi • joint torque
L max.
= lunghezza massima linee frigorifere • maximum refrigerant line lenght
H max.
= Massimo dislivello tra unità interna ed esterna • Max. difference of level between indoor and outdoor units
TAB D REINTEGRO CARICA REFRIGERANTE • REFRIGERANT RECHARGE
Mod. CX / CXA
Reintegro carica refr. • Ref. charge
Per lunghezza linee superiore a
For line lenght longer than
TAB E TARATURA DISPOSITIVO BASSA TEMPERATURA
LOW AMBIENT TEMPERATURE DEVICE SETTING
16 ± 2 [kg/cm
DCPX
1.570 ± 196 [kPa]
1807 T
12,7 x 0,81 ( 1 / 2 ")
49 ÷59
6,35 x 0,71 ( 1 / 4 ")
15 ÷20
15
7
1807 T
20 [g/m]
10 - 15 [m]
2
]
PREVEDERE IL RICCIOLO
Max. 15 m.
2407 T
15,88 x 0,81 ( 5 / 8 ")
62 ÷76
6,35 x 0,71 ( 1 / 4 ")
15 ÷20
15
7
2407 T
20 [g/m]
10 -15 [m]
2
18 [kg/cm
] = 220 V
1.766 [kPa] = 220 V
FIT A LOOP
3 m.
2
14 [kg/cm
] = 0 V
1373 [kPa] = 0 V
Max.
+7 m.
Max.
-7 m.