Operation of the room unit
The temperature is adjusted with rotary switch A. The figure on the display will flash five times and then
become set.
ECO button
User menu
To access the menu, press button C for more than 3 seconds. Move in the menus with rotary switch A
and activate the selected function with button C. The variable to be changed flashes (page 2, Figure 1).
22
The ECO function is activated by pressing the ECO button once (default setting:
8 h /20.5 ºC). When the function is engaged, the number of hours is shown in
the upper right-hand corner for 20 seconds.
When the ECO button is pressed for more than 3 seconds, the AWAY function
is activated (default setting: 30 days / 18.5 ºC). The duration of the function in
days is shown in the upper right-hand corner.
Minimum temperature for supply water
Radiator heating: min. 5–35 ºC / factory setting: min. 5 ºC
Floor heating: min. 5–35 ºC / factory setting: min. 20 ºC
Maximum temperature for supply water
Radiator heating: max. 40–95 ºC / factory setting: max. 60 ºC
Floor heating: max. 20–40 ºC / factory setting: max. 35 ºC
Time: hh, mm
Weekday number 1–7
1 = Monday, 5 = Friday, 7 = Sunday
The temperature for the ECO function is xx.y ºC and the duration is x h.
The factory setting is 20.5 ºC / 8 h.
The temperature for the AWAY function is xx.y ºC and the duration
in days is 1–30–infinite (= for now).
The factory setting is 18.5 ºC / 30 days.