CONNECT THE CABLE TO THE OUTDOOR UNIT

5
(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed fl exible cable
(see below table), type designation 60245 IEC 57 or heavier cable.
Model
WH-UD03JE5 and WH-UD05JE5
WH-UD07JE5 and WH-UD09JE5
Terminals on the indoor unit
Colour of wires
Terminals on the outdoor unit
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover back to the original position with screw.
WIRE STRIPPING AND CONNECTING REQUIREMENT
Wire stripping
No loose strand when insert

PIPE INSULATION

6
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the
insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with
thickness 6 mm or above.
10
Flexible cable specifi cation
2
4 x (1.5 mm
)
4 x (2.5 mm
2
)
1
2
3
1
2
3
Indoor/outdoor
connecting
terminal board
5 mm or more
(gap between wires)
Terminal Board
1
2
3
Holder (Clamper)
WARNING
This equipment must be properly earthed.
Conductor
Conductor
fully insert
over insert
ACCEPT
PROHIBITED
Earth Wire
must be longer
than others
cables for
safety reason.
Conductor not
fully insert
PROHIBITED