Heating and cooling curve
The heating and cooling curves for the Uponor Smatrix
Move controller is shown in the diagram below. The
diagram shows the calculated supply temperature, for
each curve, at different outdoor temperatures. The
controller uses the selected curve to operate the mixer
valve, which in turn adjusts the supply temperature to
the system.
Supply temperature
5
4,5
4
3,5
80
70
60
50
40
30
20
10
36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6
4 2
Outdoor temperature
The choice of curve depends on a combination of
different factors, such as how well insulated the house
is, geographical location, type of heating/cooling
system etc.
Example:
A poorly insulated house heated by a radiator system
requires a higher curve value than an equivalent house
with underfl oor heating.
The curves in the diagram are also limited by maximum
and minimum parameters set in the system (marked in
the diagram with extra thick lines).
U P O N O R S M AT R I X M O V E · Q U I C K G U I D E
Q U I C K G U I D E
3
2,5
2
1,5
1,2
1
0,8
0,7
0,6
0,4
0,2
0
-2 -4 -6 -8 -10 -12 -14 -16 -18 -20
To change the heating and/or cooling curve:
1. Press and hold the OK button on the controller for
about 10 seconds to enter the system parameters
menu.
2. The settings icon is displayed in the top left hand
corner of the display, and the text Hot type, Cld
type, or rEv type (depending of current operating
mode) is displayed.
3. Use buttons < or > to locate parameter 1 (Cur)
– Heating curve, or 1 (Cur) – Cooling curve. They
are identifi ed using the heating or cooling symbol.
Heating curve:
Default: 0.7
Setting range: 0.1 – 5, 0.1 increments
Cooling curve:
Default: 0.4
Setting range: 0.1 – 5, 0.1 increments
4. Use buttons - or + to change parameter setting.
5. Press the OK button on the controller to confi rm
the change and return to the system parameter
settings.
6. Repeat steps 3 through 5 to change the other curve
settings, if needed.

Factory reset

To perform a factory reset, go to system parameter 23
(ALL) – Factory reset, in the controller.
Press and hold the OK button for about 5 seconds until
the controller restarts.
See section Setup the system for more information.