HPL 9S-TU(R)W - HPL 18S-TU(R)W
4
9
Heat output COP
9.1
Heat output / COP
1. For air temperatures between -22°C and -5°C, flow temperature increasing from 45? t
2. Operation with 2 compressors
3. Operation with 1 comressor
4. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, other parameters, in
particular the defrosting capacity and regulation, should also be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for care,
commissioning and operation can be found in the relevant sections of the installation and operation instructions. The specified values have the following meaning, e.g. A7/
W35: outside air temperature 7 °C and heating water flow temperature 35 °C.
5. Standard nominal flow only possible with an electronically controlled circulating pump with actuation via heat pump manager.
6. The heat output and COP is reduced by approx. 5 % in lower operation
7. When the optional weather protection hood (accessory) is used. the sound pressure level in outlet direction is reduced by 3 dB(A).
8. The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
9. See CE declaration of conformity
10.The heat circulating pump and the heat pump manager must always be ready for operation.
11.The coefficient of performance (COP) in partial load operation can be increased by selecting "energy-optimised heating operation" (natural defrosting)
1
Type and order code
2
Design
Heat source
2.1
Model
2.2
Controller
2.3
Installation location
2.4
Thermal energy metering
2.5
Performance levels
3
Operating limits
3.1
Heating water flow / return
3.2
Air (heating)
3.2
Cooling water flow
3.3
Air (cooling)
4
4
Flow
/ sound
4.1
Heating water flow heat pump circuit / free compression
Nominal flow in accordance with EN 14511
4.2
Minimum heating water flow rate
Heat pump circuit
4.3
Cooling water flow rate / internal pressure differential
Nominal flow in accordance with EN 14511
Minimum cooling water flow rate
4.4
Sound power level according to EN 12102
Normal operation / reduced operation
4.5
Sound pressure level at a distance of 10 m (air outlet side)
Normal operation / reduced operation
4.6
Air flow
Normal operation / reduced operation
5
Dimensions, weight and filling quantities
5.1
Device dimensions without connections
5.2
Device connections for heating
5.3
Weight of the transportable unit(s) incl. packaging
5.4
Refrigerant / total filling weight
www.gdts.one
Performance level
at A-7 / W35
at A2 / W35
at A7 / W35
at A7 / W45
at A7 / W55
at A10 / W35
Haed pump / Hydro tower
1
at A7 / W35...30
at A7 / W45...40
at A7 / W55...47
A35 / W18...23
6 7
8
6 7
6
452168.66.05 · FD 9912
EN 14511
1
kW / ---
5.5 / 3.3
---
kW / ---
7.2 / 4.3
---
kW / ---
8.4 / 4.9
---
kW / ---
8.2 / 3.8
---
kW / ---
8.0 / 3.0
---
kW / ---
8.9 / 5.3
---
HPL 9S-TURW
Air
Reversible with hydro
tower
Integrated (hydro tower) Integrated (hydro tower) Integrated (hydro tower)
Outdoors / Indoors
Integrated
1
up to 60 ± 2 / from 18
°C
°C
-22 to +35
°C
+7 to +20
°C
+15 to +45
1.5 / 41000
m³/h / Pa
m³/h / Pa
1.4 / 46000
5
m³/h / Pa
0.9
/ 67000
1.2
m³/h / Pa
1.2 / 56000
m³/h / Pa
m³/h / Pa
1.2 / 56000
53 / 53
dB(A)
25 / 25
dB(A)
2700 / 2100
m³/h
H x W x L mm
1650 x 910 x 750
inches
G 1 1/4" external thread G 1 1/4" external thread G 1 1/4" external thread
kg
225
type/kg
R410A / 3.9
EN 14511
2
1
2
7.2 / 3.2
---
9.5 /
---
11
4.1(4.3)
11.3 / 4.8
---
10.8 / 3.9
---
10.0 / 3.1
---
12.0 / 5.1
---
HPL 12S-TURW
Air
Reversible with hydro
tower
Outdoors / indoors
Integrated
1
up to 60 ± 2 / from 18
-22 to +35
+7 to +20
+15 to +45
1.9 / 18000
1.8 / 24000
5
1.2
/ 55000
1.4
1.4 / 46000
1.4 / 46000
54 / 53
26 / 25
4700 / 3600
1650 x 910 x 750
265
R410A / 4.78
English
EN 14511
1
2
5.6 / 3.3
10.5 / 3.2
12.3 / 3.9
7.3 / 4.3
11
(4.0)
8.4 / 5.0
8.1 / 3.9
7.7 / 3.2
8.8 / 5.4
HPL 18S-TURW
Air
Reversible with hydro
tower
Outdoors / indoors
Integrated
2
up to 60 ± 2 / from 18
2
3
-22 to +5
/ +35
3
2
+7
/ +9
to +20
+15 to +45
1.5 / 40900
1.4 / 45900
5
1.4
/ 66900
1.4
2.2 / 8100
1.6 / 36500
54 / 53
26 / 25
5500 / 3200
1650 x 910 x 750
295
R410A / 5.9
EN-11