Installation - Galletti UTN 6 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für UTN 6:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 5
RE
Designed to meet the needs of users who wish to employ electric heating
G B
or supplement conventional water heating systems (e.g. thermal ventilating
units supplied with hot water from a heat pump), the RE supplementary heating
element module can be used on all UTN thermal ventilating units.
The RE accessory is available in the following versions:
TABLE 1
Electrical
Current
Model
input (kW)
rating (A)
UTN 6-8
2.0
8,7
UTN 12
3.0
4,3
6.0
8,7
UTN 16
4.5
6,5
9.0
13
UTN 22
4.5
6,5
9.0
13
UTN 30
9.0
13
12
17,3
The RE module shown in figure (1) is mainly composed of:
A) Armoured finned heating elements made of aluminium, complete with
supporting brackets for fastening them to the load-bearing structure of the electric
module, which is built from thick galvanised sheet steel, duly insulated and
provided with an electric control panel for housing the power relays and wire
terminals. In conformity with electric safety directives, the module is equipped with
3 automatic-reset safety devices (one for each heating element) and one manual-
reset safety device.
B) An automatic-reset safety thermostat, integral with the heating element,
which switches it off should overheating occur as a result of irregular operating
conditions or a fault in the fan motor unit;
C) A manual-reset safety thermostat, mounted on the load-bearing structure,
which switches off the heating element in the event of a simultaneous failure of
all 3 automatic-reset safety thermostats.
Caution: the sensitive element of the manual-reset safety thermostat is a capillary
bulb that must be duly re-positioned, always in the top part, if the RE module is
installed in a configuration differing from the standard one. In the standard
configuration, the box housing the electric connections is situated on the same
side as the water connections. Therefore, viewing the machine from the front after
it has been installed, the electric module will be positioned on the machine itself
with the electric box on the left side. In this configuration, the thermostat bulb will
be in the correct position (factory configuration). If the electric module is installed
in the opposite position (electric box on the right), it will be necessary to move the
thermostat bulb into the position shown in figure (2); care must be taken to fasten
it securely with clamps, using the holes provided for this purpose.
D) An electric box incorporating the power contactors, connection terminals and
manual-reset thermostat.
E) L-shaped brackets and screws for fastening the module to the machine outlet.
The RE heating element must be associated with the following control:
Control
code
Microprocessor control on ventilating unit: automatic control of
EYMICROPROD
ventilating convector, valves and heating element
+ EYSW
Power card to be added to MICRO-D and MICROPRO-D control panels
UYIPM

INSTALLATION

Warning! Before starting the installation procedure, disconnect the thermal
ventilating unit from the power supply
THE RE ELECTRIC MODULE CAN BE INSTALLED ONLY ON THE MACHINE AIR
OUTLET
The overall dimensions are shown in figures 4a and 4b.
It is recommended to mount the RE module on the thermal ventilating unit before
installing the unit itself in place.
1.
Place the thermal ventilating unit in an upright position. Fasten the L-
shaped brackets on the two short sides of the air outlet, using the 4 holes
provided (2 per side) and self-tapping screws (supplied in the kit).
2.
After applying the 2 L-shaped brackets, which serve both as a guide and
support for the RE module, you can install the module itself; make sure
that the L-shaped brackets are both positioned inside the rectangular
outlet.
3.
Apply the self-tapping screws (supplied in the kit) as shown in figure (3):
the screws on the short sides act on the L-shaped brackets, while on the
two long sides holes are provided for fastening the module directly to the
outlet of the thermal ventilating unit.
Power supply
(V - f- Hz)
230-1-50
400-3-50
400-3-50
400-3-50
400-3-50
Description of controls
NOTE:
The electric module has holes like those on the machine air intake, on the
extremity turned toward the air outflow ducts. This allows you to attach all the
accessories that can be directly applied on the machine (PCOC, PCOF, GAT,
etc...).
Important: if you wish to install vibration-damping couplings use ONLY GAT
heat-resistant couplings
After fastening the electric module to the thermal ventilating unit, you can position
the latter in its final installation site and proceed with the wiring (see MICROPRO-
D manual).
Each thermal-ventilating unit requires a switch (IL) on the feeder line with a
distance of at least 3 mm between the opening contacts, and a suitable safety fuse
(F).
I) Open the electric box by loosening the 4 self-tapping screws on the front of the
cover.
II) Connect the electric wires, using the wire clamps provided, both for the power
supply line and the wire connecting to the control on the wall.
Important: The only control provided is the MICROPRO-D, which incorporates all
the necessary functions for managing the thermal ventilating unit, the heating
elements (and the on-off valves on the water side, where present).
NOTE: the MICROPRO-D control guarantees the complete safety of the RE
module, thanks to the POST-VENTILATION function, which keeps the fan
running for 2 minutes after the heating elements have been switched off
because the set temperature point has been reached. This feature serves to
prevent dangerous overheating which may be caused by the thermal inertia
of the heating elements themselves.
Galletti S.p.A. will not be liable for any faults or damage caused by improper use
of the RE module and/or an inadequate control panel.
If the module is applied on thermal ventilating units with plumbing connections
on the right (i.e. with the electric box on the right) it will be necessary to change
the position of the bulb of the manual-reset safety thermostat.
As noted above in item (C), if the electric module is installed in a position opposite
to the factory configuration, it will be necessary to move the thermostat bulb into
the position shown in figure (2); care must be taken to fasten it securely with
clamps, using the holes provided for this purpose.
In case of vertical installation, the safety thermostat bulb must be secured to
the wires of the automatic-reset safety thermostat (see fig 1 B) using the
clamps provided in the kit.
Warning: the control panel must be mounted on the wall in an easily accessible
position allowing the user to set the functions while ensuring an accurate reading
of the ambient temperature. Therefore, avoid:
- positions directly exposed to sunlight;
- positions exposed to direct currents of warm or cold air;
- placing obstacles that impede an accurate temperature reading (drapes or
furniture);
- constant presence of steam
- covering the panel or building it into the wall.
The minimum gauges of the power cables will depend on the electrical inputs
specified in table 1, in compliance with current regulations.
To guarantee the efficiency of a thermal ventilating unit fitted with a supplementary
RE heating element module, comply with the following directions:
- keep the air filter clean;
- do not pour liquids inside the equipment;
- make absolutely sure you do not obstruct the air outlet or inlet of the thermal
ventilating unit;
HOW TO ORDER
Code
Name
Description
UYRE06M2
RE06M2 Single-phase electric heating element module,
safety devices, power relays, models UTN 06, 08
UYRE12T3
RE12T3
Three-phase electric heating element module,
safety devices, power relays, model UTN 12
UYRE12T6
RE12T6
Three-phase electric heating element module,
safety devices, power relays, model UTN 12
UYRE16T4
RE16T4
Three-phase electric heating element module,
safety devices, power relays, model UTN 16
UYRE16T9
RE16T9
Three-phase electric heating element module,
safety devices, power relays, model UTN 16
UYRE22T4
RE22T4
Three-phase electric heating element module,
safety devices, power relays, model UTN 22
UYRE22T9
RE22T9
Three-phase electric heating element module,
safety devices, power relays, model UTN 22
UYRE30T9
RE30T9
Three-phase electric heating element module,
safety devices, power relays, model UTN 30
UYRE30T12
RE30T12 Three-phase electric heating element module,
safety devices, power relays, model UTN 30
3
UT66000337 - rev. 01