Herunterladen Diese Seite drucken

janitza UMG 604-PRO Installationsanleitung Seite 12

Power analyser
Vorschau ausblenden Andere Handbücher für UMG 604-PRO:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

11
Operation and button functions
Operation and button functions
11
Current transformer ratio configuration
15
Current transformer ratio configuration
15
The device is operated using buttons 1 and 2.
The device is operated using buttons 1 and 2.
The service button is designated for use by
The service button is designated for use by
Current transformer ratios can be assigned to each
Current transformer ratios can be assigned to each
trained service employees only.
trained service employees only.
of the 4 current transformer inputs on the device.
of the 4 current transformer inputs on the device.
The factory setting is 5 A/5 A.
The factory setting is 5 A/5 A.
The device differentiates between display and
The device differentiates between display and
In addresses 000 and 001
In addresses 000 and 001
programming mode (see step 12).
programming mode (see step 12).
• program the same current transformer ratios for
• program the same current transformer ratios for
Button intervals:
Button intervals:
all 4 phases.
all 4 phases.
Press the appropriate button for a short time:
Press the appropriate button for a short time:
• current transformer ratios that are entered
• current transformer ratios that are entered
• Scroll forwards.
• Scroll forwards.
overwrite addresses 010 to 041.
overwrite addresses 010 to 041.
• Digit/value +1.
• Digit/value +1.
In addresses 010 to 041
In addresses 010 to 041
Press the appropriate button for a long time:
Press the appropriate button for a long time:
• program current transformer ratios individually
• program current transformer ratios individually
• Scroll backwards.
• Scroll backwards.
for each phase.
for each phase.
• Digit/value -1.
• Digit/value -1.
The device handles programmed values in
The device handles programmed values in
addresses 010 to 041 with priority, whereupon it
addresses 010 to 041 with priority, whereupon it
To switch between display mode and
To switch between display mode and
sets addresses 000 and 001 to 0.
sets addresses 000 and 001 to 0.
programming mode, press and hold both
programming mode, press and hold both
The programming procedure for current transformer
The programming procedure for current transformer
buttons simultaneously for 1 second.
buttons simultaneously for 1 second.
ratios works in the same way as the procedure for
ratios works in the same way as the procedure for
voltage transformer ratios (see step 14).
voltage transformer ratios (see step 14).
The device switches from programming mode
The device switches from programming mode
to display mode if
2 connection variants for measuring the device's current:
to display mode if
2 connection variants for measuring the device's current:
• no buttons are pressed for 60 seconds.
• no buttons are pressed for 60 seconds.
Connection variant 0: Current measurement
Connection variant 0: Current measurement
• buttons 1 and 2 are pressed simultaneously
• via 3 current transformers in 3-phase 4-conductor
• buttons 1 and 2 are pressed simultaneously
• via 3 current transformers in 3-phase 4-conductor
for 1 second.
for 1 second.
networks.
networks.
• via 2 current transformers in networks with the
• via 2 current transformers in networks with the
same loading.
C
same loading.
C
NOTE!
NOTE!
• in single-phase 3-conductor systems.
• in single-phase 3-conductor systems.
Changes are only applied after exiting
Changes are only applied after exiting
Connection variant 1: Current measurement
Connection variant 1: Current measurement
programming mode.
programming mode.
• via 2 current transformers (Aron circuit) in
• via 2 current transformers (Aron circuit) in
3-phase 3-conductor networks.
3-phase 3-conductor networks.
Configuring the device as a "DHCP client" or with a "Static IP address"
Configuring the device as a "DHCP client" or with a "Static IP address"
17
17
To configure the device as a "DHCP client" or
To configure the device as a "DHCP client" or
with a "Static IP address", first set address 205
with a "Static IP address", first set address 205
Digital inputs
Digital inputs
(DHCP mode):
(DHCP mode):
2 digital inputs.
2 digital inputs.
Pulse input (S0):
Pulse input (S0):
1. Switch to programming mode as described
1. Switch to programming mode as described
Maximum counter frequency
20 Hz
Maximum counter frequency
20 Hz
(the first digit flashes).
Switching input:
(the first digit flashes).
Switching input:
2. Use button 2 to select the value 2.
Response time (Jasic program)
2. Use button 2 to select the value 2.
200 ms
Response time (Jasic program)
200 ms
18 V to 28 V DC
3. Use button 1 to move to the second digit.
18 V to 28 V DC
3. Use button 1 to move to the second digit.
Input signal present
Input signal present
(typical 4 mA)
(typical 4 mA)
4. Use button 2 to select the value 0.
4. Use button 2 to select the value 0.
0 to 5 V DC,
0 to 5 V DC,
Input signal not present
Input signal not present
5. Use button 1 to move to the third digit.
current less than 0.5 mA
current less than 0.5 mA
5. Use button 1 to move to the third digit.
6. Use button 2 to select the value 5.
6. Use button 2 to select the value 5.
Digital outputs
Digital outputs
7. Address 205 is shown on the display.
7. Address 205 is shown on the display.
2 digital outputs, semiconductor relay, not short-circuit proof.
2 digital outputs, semiconductor relay, not short-circuit proof.
8. Use button 1 to move to the settings for
Switching voltage
8. Use button 1 to move to the settings for
max. 30 V AC, 60 V DC
Switching voltage
max. 30 V AC, 60 V DC
Switching current
the DHCP mode content.
max. 50 mA
Switching current
the DHCP mode content.
max. 50 mA
RMS
Response time (Jasic program)
200 ms
Response time (Jasic program)
200 ms
Output of voltage dips
20 ms
Output of voltage dips
20 ms
Then select the "DHCP client" or the "Static IP
Then select the "DHCP client" or the "Static IP
Output of
Output of
20 ms
address" in DHCP mode as follows:
address" in DHCP mode as follows:
20 ms
voltage exceedance events
voltage exceedance events
Pulse output (energy pulse)
max. 20 Hz
Pulse output (energy pulse)
max. 20 Hz
Temperature measurement input
Temperature measurement input
3-wire measurement.
3-wire measurement.
Update time
approx 200 ms
Update time
approx 200 ms
Connectable sensors
PT100, PT1000, KTY83, KTY84
Connectable sensors
PT100, PT1000, KTY83, KTY84
Total burden (sensor + cable)
Total burden (sensor + cable)
max. 4 kOhm
max. 4 kOhm
Cable length (Residual current monitoring, digital
Cable length (Residual current monitoring, digital
C
C
NOTE!
NOTE!
inputs and outputs, temperature measurement input)
inputs and outputs, temperature measurement input)
Ensure that address 204 (RS232 mode) has the value 0 (default setting) to operate the device
Ensure that address 204 (RS232 mode) has the value 0 (default setting) to operate the device
Up to 30 m (32.81 yd)
Unshielded
Up to 30 m (32.81 yd)
Unshielded
in DHCP client mode!
in DHCP client mode!
More than 30 m (32.81 yd)
Shielded
More than 30 m (32.81 yd)
Shielded
Temperature
2 digital inputs
Temperature
measurement input
2 digital outputs
measurement input
Addr.
Current transformer values
Addr.
Current transformer values
RS232 RS485
RS232 RS485
000
L1 L2 L3 L4 (primary)
000
L1 L2 L3 L4 (primary)
Supply voltage
001
L1 L2 L3 L4 (secondary)
001
L1 L2 L3 L4 (secondary)
A B
010
L1 (primary)
A B
010
L1 (primary)
011
011
L1 (secondary)
L1 (secondary)
020
L2 (primary)
020
L2 (primary)
021
L2 (secondary)
021
L2 (secondary)
030
L3 (primary)
030
L3 (primary)
031
L3 (secondary)
031
L3 (secondary)
040
L4 (primary)
040
L4 (primary)
041
L4 (secondary)
041
L4 (secondary)
Parameter list excerpt of "current transformer values"
Parameter list excerpt of "current transformer values"
Addr.
Current measurement connection variant
Addr.
Current measurement connection variant
4 x current measurement 4 x voltage measurement
4 x current measurement 4 x voltage measurement
0 = 3 current transformers and
0 = 3 current transformers and
Ethernet interface
Button 1 and button 2
Ethernet interface
accompanying variants (factory
accompanying variants (factory
Profibus (option)
setting)
110
Profibus (option)
setting)
110
Display
Display
Service button
1 = 2 current transformers
Service button
1 = 2 current transformers
(Aron circuit)
(Aron circuit)
Parameter list excerpt of "current transformer connection variants"
Parameter list excerpt of "current transformer connection variants"
C
C
NOTE!
NOTE!
C
C
For further information on button
NOTE!
For further information on button
NOTE!
For further information on current
functions and parameter settings,
For further information on current
functions and parameter settings,
see the user manual.
transformer ratios, see the user
see the user manual.
transformer ratios, see the user
manual.
manual.
• Set "DHCP client"
• Set "DHCP client"
(default setting)
(default setting)
RS232 interface
RS232 interface
1. Use button 2 to select value 2, "DHCP
1. Use button 2 to select value 2, "DHCP
5 pin screw-type terminals.
5 pin screw-type terminals.
client" (see table in step 16).
client" (see table in step 16).
Protocol
Modbus RTU/slave
Protocol
Modbus RTU/slave
2. Press button 1 to confirm your entry.
2. Press button 1 to confirm your entry.
9.6 kbps, 19.2 kbps,
9.6 kbps, 19.2 kbps,
3. The address display flashes.
3. The address display flashes.
Transmission rate
38.4 kbps, 57.6 kbps,
Transmission rate
38.4 kbps, 57.6 kbps,
115.2 kbps.
115.2 kbps.
You can continue to configure the addresses.
You can continue to configure the addresses.
RS485 interface
RS485 interface
• Setting the "Static IP address"
2 pin screw-type terminals.
• Setting the "Static IP address"
2 pin screw-type terminals.
1. Use button 2 to select value 0,
1. Use button 2 to select value 0,
Modbus RTU/slave,
Modbus RTU/slave,
Protocol
Protocol
Modbus RTU/master,
Modbus RTU/master,
"Static IP" (see table in step 16).
"Static IP" (see table in step 16).
9.6 kbps, 19.2 kbps,
9.6 kbps, 19.2 kbps,
2. Press button 1 to confirm your entry.
2. Press button 1 to confirm your entry.
Transmission rate
38.4 kbps, 57.6 kbps,
Transmission rate
38.4 kbps, 57.6 kbps,
3. The address display flashes.
115.2 kbps, 921.6 kbps
3. The address display flashes.
115.2 kbps, 921.6 kbps
AC/DC
You can continue to configure the addresses.
AC/DC
You can continue to configure the addresses.
RMS
RS485 interface (optional)
RS485 interface (optional)
Connector, SUB D 9 pin
Connector, SUB D 9 pin
Profibus DP/V0
Profibus DP/V0
Protocol, profibus (optional)
Protocol, profibus (optional)
according to EN 50170
according to EN 50170
Transmission rate
9.6 kbaud up to 12 Mbaud
Transmission rate
9.6 kbaud up to 12 Mbaud
Ethernet interface 10/100Base-TX (optional)
Ethernet interface 10/100Base-TX (optional)
Connection
RJ45
Connection
RJ45
Modbus gateway,
Modbus gateway,
Function
Function
embedded Webserver (HTTP)
embedded Webserver (HTTP)
TCP/IP, EMAIL (SMTP),
TCP/IP, EMAIL (SMTP),
DHCP-Client (BootP),
DHCP-Client (BootP),
Modbus/TCP (Port 502),
Modbus/TCP (Port 502),
Protocols
Protocols
Modbus RTU over Ethernet
Modbus RTU over Ethernet
(Port 8000), FTP, ICMP (Ping),
(Port 8000), FTP, ICMP (Ping),
FTP, SNMP, NTP, TFTP.
FTP, SNMP, NTP, TFTP.
12
Display mode
Display mode
12
Configure the Ethernet connection
16
Configure the Ethernet connection
16
2 digital inputs
After the power returns, the device is in display
After the power returns, the device is in display
2 digital outputs
mode. In display mode:
mode. In display mode:
Static IP address (Addr. 205, content = 0)
Static IP address (Addr. 205, content = 0)
• Use button 1 to select the phase for the
• Use button 1 to select the phase for the
In networks without a DHCP server, select the
In networks without a DHCP server, select the
measured values.
measured values.
Supply voltage
network address (see table) on the device.
network address (see table) on the device.
• Use button 2 to scroll between the measured
• Use button 2 to scroll between the measured
values for current, voltage, power, etc.
values for current, voltage, power, etc.
BootP (Addr. 205, content = 1)
BootP (Addr. 205, content = 1)
BootP enables a device to be integrated into
BootP enables a device to be integrated into
N L1
an existing network fully automatically. However,
an existing network fully automatically. However,
BootP is an older protocol and does not provide
BootP is an older protocol and does not provide
the scope of functions provided by DHCP.
the scope of functions provided by DHCP.
DHCP client (Addr. 205, content = 2)
DHCP client (Addr. 205, content = 2)
DHCP makes it possible integrate a device into
DHCP makes it possible integrate a device into
RxD TxD
an existing network automatically without the
an existing network automatically without the
need for any additional configuration.
need for any additional configuration.
Fig. Display example for "Display mode",
When started, the device automatically obtains
When started, the device automatically obtains
measured value displayed: U L1-N = 230.0V.
the IP address, the subnet mask and the
the IP address, the subnet mask and the
gateway from the DHCP server. The device's
gateway from the DHCP server. The device's
C
C
NOTE!
Button 1 and button 2
default setting is "DHCP client".
default setting is "DHCP client".
For further information
• on measured value indications and
the factory settings
• on parameter lists and addresses
• on the display password
is provided in the user manual.
Configuring the "Static IP address"
Configuring the "Static IP address"
18
18
If the device is accessed via a "Static IP address",
If the device is accessed via a "Static IP address",
the device requires settings for the:
the device requires settings for the:
Terminal connection capacity (supply voltage)
Terminal connection capacity (supply voltage)
1. Device IP address.
1. Device IP address.
Connectable conductors. Connect one conductor per terminal!
Connectable conductors. Connect one conductor per terminal!
2. Subnet mask.
2. Subnet mask.
Single core, multi-core,
Single core, multi-core,
3. Gateway address (not required for
fine-stranded
3. Gateway address (not required for
fine-stranded
configuration).
Cable end sleeve (not insulated)
configuration).
Cable end sleeve (not insulated)
(see the table in step 16)
(see the table in step 16)
Cable end sleeve ( insulated)
Cable end sleeve ( insulated)
Stripping length
Stripping length
1. Setting the device IP address
1. Setting the device IP address
Terminal connection capacity (voltage measurement)
• Switch to programming mode
Terminal connection capacity (voltage measurement)
• Switch to programming mode
Conductors to be connected. Only one conductor can be con-
Conductors to be connected. Only one conductor can be con-
(see step 12).
nected per terminal!
nected per terminal!
• Select address 300 and enter the first
• Select address 300 and enter the first
Single core, multi-core, fine-
Single core, multi-core, fine-
3 characters of the device
stranded
stranded
IP address (see the table in step 16).
Cable end sleeve (not insulated)
Cable end sleeve (not insulated)
• Select address 301 and enter the second
• Select address 301 and enter the second
Cable end sleeve (insulated)
Cable end sleeve (insulated)
3 characters of the device
Stripping length
Stripping length
IP address.
• Complete the entries for addresses 302
• Complete the entries for addresses 302
Terminal connection capacity (current measurement)
Terminal connection capacity (current measurement)
and 303.
Conductors to be connected. Only one conductor can be con-
Conductors to be connected. Only one conductor can be con-
nected per terminal!
nected per terminal!
Single core, multi-core, fine-
Single core, multi-core, fine-
stranded
stranded
Cable end sleeve (not insulated)
Cable end sleeve (not insulated)
Cable end sleeve (insulated)
Cable end sleeve (insulated)
Stripping length
Stripping length
C
C
NOTE!
Further technical data can be found in
the user manual for the device.
12 / 14
Programming mode
Programming mode
The most important settings on the device
The most important settings on the device
are carried out in programming mode (PRG).
are carried out in programming mode (PRG).
Addr.
204
N L1
205
V
V
300
301
Fig. Display example for "Programming mode",
address 000 with a content of 5.000.
302
Input Output
L1 L2 L3 L4
RxD TxD
Input Output
L1 L2 L3 L4
303
When you press and hold buttons 1 and 2
When you press and hold buttons 1 and 2
304
Fig. Display example for "Display mode",
simultaneously for approx. 1 second, the device
simultaneously for approx. 1 second, the device
measured value displayed: U L1-N = 230.0V.
305
switches to programming mode as long as no
switches to programming mode as long as no
306
display password has been configured:
display password has been configured:
NOTE!
307
• The text "PRG" is shown on the display.
For further information
• The first digit in the address flashes.
310
• on measured value indications and
311
the factory settings
C
312
• on parameter lists and addresses
313
• on the display password
is provided in the user manual.
2. Set the subnet mask
• Select the subnet mask via addresses
Terminal connection capacity: Digital inputs and outputs
Terminal connection capacity: Digital inputs and outputs
Connectable conductors. Connect one conductor per terminal!
Connectable conductors. Connect one conductor per terminal!
Single core, multi-core, fine-
Single core, multi-core, fine-
0.08 - 2.5 mm
2
, AWG 28-12
0.08 - 2.5 mm
2
, AWG 28-12
stranded
stranded
0.20 - 1.5 mm2, AWG 24 - 16
0.20 - 1.5 mm2, AWG 24 - 16
Cable end sleeve (not insulated)
Cable end sleeve (not insulated)
3. Set the standard gateway
0.25 - 1.5 mm
, AWG 24-16
0.25 - 1.5 mm
2
2
, AWG 24-16
Cable end sleeve (insulated)
Cable end sleeve (insulated)
• Select the standard gateway (if present) via
5-6 mm (0.2 - 0.24 in)
5-6 mm (0.2 - 0.24 in)
Tightening torque
Tightening torque
Stripping length
Stripping length
(see step 12).
Terminal connection capacity (RS 232 / RS 485)
Terminal connection capacity (RS 232 / RS 485)
Example:
Example:
Connectable conductors. Connect one conductor per terminal!
Connectable conductors. Connect one conductor per terminal!
0.08 - 4.0 mm
, AWG 28-12
0.08 - 4.0 mm
2
2
, AWG 28-12
Device IP address: 192.168.1.116
3 characters of the device
Device IP address: 192.168.1.116
Single core, multi-core, fine-
Single core, multi-core, fine-
Subnet mask:
IP address (see the table in step 16).
stranded
Subnet mask:
0.25 - 2.5 mm
, AWG 24-14
stranded
0.25 - 2.5 mm
2
2
, AWG 24-14
Cable end sleeve (not
Cable end sleeve (not
0.25 - 2.5 mm
, AWG 24-14
0.25 - 2.5 mm
2
, AWG 24-14
2
insulated)
In this case, set the computer as follows:
insulated)
3 characters of the device
In this case, set the computer as follows:
8-9 mm (0.31 - 0.35 in)
8-9 mm (0.31 - 0.35 in)
IP address.
Cable end sleeve (insulated)
IP address:
IP address:
Cable end sleeve (insulated)
Subnet mask:
Subnet mask:
Tightening torque
Tightening torque
and 303.
Stripping length
Stripping length
C
0.08 - 4.0 mm
, AWG 28-12
0.08 - 4.0 mm
2
, AWG 28-12
2
Terminal connection capacity: temperature measurement input
Terminal connection capacity: temperature measurement input
Connectable conductors. Connect one conductor per terminal!
0.25 - 4.0 mm
0.25 - 4.0 mm
2
, AWG 28-14
, AWG 28-14
Connectable conductors. Connect one conductor per terminal!
2
Single core, multi-core, fine-
Single core, multi-core, fine-
0.25 - 2.5 mm
0.25 - 2.5 mm
2
, AWG 24-14
, AWG 24-14
2
stranded
stranded
8-9 mm (0.31 - 0.35 in)
8-9 mm (0.31 - 0.35 in)
Cable end sleeve (not insulated)
Cable end sleeve (not insulated)
Cable end sleeve (insulated)
Cable end sleeve (insulated)
NOTE!
Tightening torque
Tightening torque
Further technical data can be found in
Stripping length
Stripping length
the user manual for the device.
Designation
Addr.
Designation
RS232, mode
RS232, mode
0 = Modbus RTU/slave
0 = Modbus RTU/slave
204
(default setting)
PRG
(default setting)
PRG
3 = Debug
3 = Debug
6 = SLIP
6 = SLIP
DHCP mode
DHCP mode
Address
0 = static IP address 1 = BootP
Content
205
Address
0 = static IP address 1 = BootP
Content
2 = DHCP client
2 = DHCP client
IP address,
xxx --- --- ---
300
IP address,
xxx --- --- ---
IP address,
--- xxx --- ---
301
IP address,
--- xxx --- ---
Fig. Display example for "Programming mode",
address 000 with a content of 5.000.
IP address,
--- --- xxx ---
302
IP address,
--- --- xxx ---
303
IP address,
IP address,
--- --- --- xxx
--- --- --- xxx
IP mask,
xxx --- --- ---
304
IP mask,
xxx --- --- ---
IP mask,
--- xxx --- ---
305
IP mask,
--- xxx --- ---
IP mask,
--- --- xxx ---
306
IP mask,
--- --- xxx ---
IP mask,
--- --- --- xxx
307
IP mask,
--- --- --- xxx
• The text "PRG" is shown on the display.
• The first digit in the address flashes.
IP gateway,
xxx --- --- ---
310
IP gateway,
xxx --- --- ---
IP gateway,
--- xxx --- ---
311
IP gateway,
--- xxx --- ---
C
IP gateway,
--- --- xxx ---
312
IP gateway,
--- --- xxx ---
NOTE!
NOTE!
IP gateway,
--- --- --- xxx
You can make further settings in the
313
IP gateway,
--- --- --- xxx
You can make further settings in the
GridVis® software.
GridVis® software.
2. Set the subnet mask
• Select the subnet mask via addresses
304 - 307 in the same way as the
304 - 307 in the same way as the
settings for the device IP address
settings for the device IP address
0.20 - 1.5 mm
2
, AWG 24-16
0.20 - 1.5 mm
2
, AWG 24-16
(see the table in step 16).
(see the table in step 16).
0.20 - 1.5 mm
2
, AWG 24-16
0.20 - 1.5 mm
2
, AWG 24-16
3. Set the standard gateway
0.20 - 1.0 mm
2
, AWG 24-18
0.20 - 1.0 mm
2
, AWG 24-18
• Select the standard gateway (if present) via
0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
addresses 310 - 313 in the same way as
addresses 310 - 313 in the same way as
7 mm (0.2756 in)
7 mm (0.2756 in)
the IP address (see the table in step 16).
the IP address (see the table in step 16).
0.20 - 1.5 mm
, AWG 24-16
0.20 - 1.5 mm
2
, AWG 24-16
2
255.255.255.0
255.255.255.0
0.20 - 1.5 mm
0.20 - 1.5 mm
2
, AWG 24-16
, AWG 24-16
2
192.168.1.117
0.20 - 1.0 mm
192.168.1.117
2
, AWG 24-18
0.20 - 1.0 mm
2
, AWG 24-18
255.255.255.0
255.255.255.0
0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
7 mm (0.2756 in)
7 mm (0.2756 in)
C
NOTE!
NOTE!
For more information about connection
For more information about connection
and communication of your device with
and communication of your device with
the software, see the quick guide of
the software, see the quick guide of
0.20 - 1.5 mm
0.20 - 1.5 mm
2
, AWG 24-16
, AWG 24-16
software GridVis®.
2
software GridVis®.
0.20 - 1.5 mm
2
, AWG 24-16
0.20 - 1.5 mm
2
, AWG 24-16
0.20 - 1.0 mm
2
, AWG 24-18
0.20 - 1.0 mm
2
, AWG 24-18
0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
7 mm (0.2756 in)
7 mm (0.2756 in)
13
19

Werbung

loading