TECHNICAL DATA

MODEL
CODE
OUTPUT
(1)
FUEL
- net calorific value
- absolute density
- max. delivery
- pressure at max. delivery
(2)
OPERATION
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
Running current
Start-up current
IGNITION TRANSFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
IN CONFORMITY WITH EEC DIRECTIVES
NOISE LEVELS
(3)
APPROVAL
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m s.l.m.
(2) Pressure at test point 17)(A)p.8, with zero pressure in the combustion chambre and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
COUNTRY
SE - FI - AT - GR - DK - ES - GB -
IT - IE - PT - IS - CH - NO
DE
NL
FR
BE
LU

ACCESSORIES

(optional):
OUTPUT POWER REGULATOR KIT: Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates
between the low and high flame output positions, thus ensuring stable operating conditions in terms of temperature or pressure. Two components
should be ordered: • Power regulator to install to the burner • Probe to install to the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
EXTENDED COMBUSTION HEAD KIT: length L = 503 mm.
TUBES KIT: cod. 3010249
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valve,
pressure governor and filter): see page 18.
kW
2nd stage
(MIN.-MAX.)
Mcal/h
kW
1st stage
(MIN.)
Mcal/h
NATURAL GAS: G20 - G21 - G22 - G23 - G25
3
kWh/Nm
Mcal/
3
Nm
3
kg/Nm
3
Nm
/h
mbar
• On-Off (1 stop min each 24 hours).
• Progressive two-stage or modulating by kit (see ACCESSOIRES).
Boilers: water, steam, diathermic oil
°C
°C max
V
Hz
rpm
W
V
A
A
V1 - V2
I1 - I2
W max
dBA
CE
CATEGORY
I
2H
I
2ELL
I
2L
I
2Er
I
2E(R)B
I
2E
Range
- 100...+500°C
0...2.5 bar
0...16 bar
6
RS 160/M BLU
3788002 - 3788004
3788003 - 3788005
930 - 1860
800 - 1600
G20
G25
10
8,6
8,6
7,4
0,71
0,78
186
216
18
24
0 - 40
400 with neutral ~ +/-10%
50 - three-phaes
2800
4500
400
9,1
72,8
230 V - 1 x 8 kV
1 A - 20 mA
4800
IP 44
90/396 - 89/336 - 2004/108 - 73/23 - 2006/95
80,5
0085 BM 0452

VARIANTS

Burner
code
3788002 - 3788004
20011680 - 20011683
3788003 - 3788005
20011682 - 20011684
Model
Code
3788002 - 3788004
RS 160/M
3788003 - 3788005
20011680 - 20011683
RS 160/M
20011682 - 20011684
PROBE
Type
Code
PT 100
3010110
Output probe
3010213
4...20 mA
3010214
Important:
The installer is responsible for the addition of any safety device not
forseen in the present manual.
20011680 - 20011683
20011682 - 20011684
300
258
60
230 with neutral ~ +/-10%
50 - three-phaes
2800
4500
230
15,8
126
Blast tube lenght
mm
373
503
Power supply
electrical
400 V
230 V
POWER REGULATOR
Type
Code
RWF40
3010212
GB

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

843 tRs 160/m bluRs 160/m blu typ 843 t

Inhaltsverzeichnis