- To remove the main pan.
- Open and remove the intake grille on the nozzle (Fig. 18, a).
- Loosen the 4 bolts (Fig. 18, d).
- Pivot the 4 bolts holding the nozzle in position (Fig. 18, c).
- Remove the panel (Fig. 18, d).
- Remove the 4 brackets (8 bolts) (Fig. 18, e)
- Swivel the pan (approximately 30°) downwards (Fig. 18, f) and release it from its
retaining lugs. (Fig. 18, g)
To refit, perform the operation in reverse order.

5.3. Fan motor assembly

From time to time, check that the turbines and the motor are clean. If necessary,
clean them using a vacuum cleaner, taking care to ensure they are not damaged.
The electric motor's bearings are lubricated for life and do not require specific
maintenance.
● Removing the fan motor assembly:
- Open the electrics box
- Disconnect the wires which form the fan motor assembly bundle.
- Follow the same procedure as for disassembling the main pan (Fig. 18) (see
section 5.2 Condensate drain pans)
- Use a screwdriver to undo the screw securing the turbine and its foolproofing
device (Fig. 19), and remove the turbine
- Remove the grommet cap (Fig. 20, a)
- Pull the fan motor assembly bundle towards the interior of the box
- Undo the 3 motor retaining screws and remove the motor (Fig. 20, b).
To refit, perform the operation in reverse order.

5.4. Heat exchange coil

A clean coil is crucial to the efficiency of the unit. If necessary, clean the coil with a
vacuum cleaner.
If the coil must be disassembled on account of a leak:
Disconnect the electrical supply to the unit before carrying out any work.
● Removing the coil:
- Insulate the unit hydraulically from the network and drain the coil.
- Disconnect the coil inlets and outlets
- Next, follow the same procedure as for disassembling the main pan (Fig. 18) and
the fan motor assembly (Fig. 20) (see sections 5.2 Condensate drain pans and
5.3 Fan motor assembly)
- Undo the 2 screws on the coil retaining clamp (Fig. 21, a) and the coil connecting
plate screw (Fig. 21, b).
- Remove the coil.
To refit, perform the operation in reverse order, remembering to bleed the coil before
refilling with water.

5.5. Return/discharge panel

Wipe the walls with a damp, slightly soapy sponge and buff them using a soft,
dry cloth.
Never use abrasive products.