Herunterladen Inhalt Inhalt Diese Seite drucken

Data Plate (Fig. 2) - CIAT COADIS LINE 600 Benutzerhandbuch

Vorschau ausblenden Andere Handbücher für COADIS LINE 600:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 50

3.1. Data plate (Fig. 2)

1 - Code
2 - Serial number
3 - Description of the unit
4 - Rated motor output
5 - Motor rotation speed
6 - Coil type
7 - Wiring diagram reference
The data plate contains all the information required to identify the unit and its
configuration. This plate is positioned on the technical face containing all the
connections, above the fresh air inlet.
Before contacting us, please note the serial no. and the designation.
IMPORTANT:
This device may be used by children aged eight and over, and by persons with limited
physical, sensory or mental capabilities, or by persons with insufficient experience or
knowledge, provided that they are being correctly supervised or provided they have
received instructions on how to use the device in complete safety, ensuring that they
have a full understanding of any risks involved. Children must not be allowed to play
with the device. User cleaning and maintenance must not be performed by children.
During normal use, this device is intended to operate under the following site
conditions:
- Maximum altitude: 2000 m,
- Minimum and maximum storage temperatures; -20°C + 65°C,
- Minimum and maximum operating temperatures; 0°C +40°C,
- Indoor return air maximum humidity level:
27°C DB (dry bulb) at 65% RH (relative humidity),
- Clean interior environment (no oxidizing agents present).
The device requires protection from any form of impact during use. Protection rating
IP 20 IK02.
This device is designed to operate in an over-voltage category II and pollution degree 2
environment, in accordance with IEC standard 664-1.
To ensure a pollution degree 2 environment, the device must be protected from water
and oil splashes, and the dust allowed to settle on it must be limited.
8 - Motor speed wiring
9 - Maximum service pressure
10 - E lectric heater specifications
(if fitted).
11 - EC declaration number
12 - Refer to the installation instructions
EN - 2