Procedure
NOTICE
The measuring result is error-free only if the differential pressure lines
same temperature. The zero calibration must be repeated if required if these conditions are fulfilled. If the shut-off valves
and the differential pressure valves
possibility of the transmitter
To commission the transmitter for vapor, proceed as follows:
1. Open both the shut-off valves
2. Open the stabilizing valve
3. Wait until the steam in the differential pressure lines
4. Open the differential pressure valve
condensate escapes without bubbles.
5. Close the vent valve.
6. Open the vent valve on the negative side of the transmitter
7. Close the differential pressure valve
8. Open the differential pressure valve
9. Close the vent valve on the negative side
10. Open the differential pressure valve
11. Check and if required correct the zero point in case of start of scale value 0 bar (4 mA).
12. Close the stabilizing valve
13. Fully open the differential pressure valves
14. You can briefly open the drain valves
6

Service and maintenance

6.1
Basic safety instructions
WARNING
Impermissible repair of explosion protected devices
Danger of explosion in areas subject to explosion hazard.
● Repair must be carried out by Siemens authorized personnel only.
WARNING
Impermissible accessories and spare parts
Danger of explosion in areas subject to explosion hazard.
● Only use original accessories or original spare parts.
● Observe all relevant installation and safety instructions described in the instructions for the device or enclosed with the
accessory or spare part.
SITRANS P500 with HART
A5E02344532-03, 04/2013
are open at the same time and the stabilizing valve
being damaged due to the streaming vapor.
at the pressure tapping point.
.
and the vent valve on the positive side of the transmitter
.
slightly, until condensate escapes without bubbles, then close it.
.
by rotating it in half a turn.
.
and
to clean the line. Close before steam starts to leak.
have equally high condensate columns with the
and in the equalizing vessels
slightly, until condensate escapes without bubbles.
.
is opened, there is a
has condensed.
slightly, until
23