14 EN – USA quick installation guide
6. Connect the grounding conductors to the grounding terminals. Connect the
conductors of the input and motor cables. Tighten the screws. See figures
(R3)..., ...F (R6)...
Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W
terminals and the phase conductors of the input cable to the L1, L2 and L3
terminals.
If the protective PE conductor is smaller than 10 mm
earthing conductor (6a). See the hardware manual for more information.
7. Frame R6 types bigger than -040A-x: Cut tabs in the shroud for the installed
cables. Frame R8: Install the side plates if removed. Knock out holes in the
EN
shroud for the input cables. See figure
8. Frames R6 and R8:; Install the shroud on the power cable terminals.
USA
G – Connect the control cables
DE
Procedure:
ES
1. Remove the front cover(s) if not already removed.
FI
2. Frame R3: Lift the control panel holder up. See figure
FR
3. Remove the rubber grommets from the bottom plate for the cable conduits to be
installed.
FR
4. Attach the cable conduits to the bottom plate holes.
NL
5. Strip the cable ends and cut to suitable length (note the extra length of the
grounding conductors).
PL
6. Route the cables. Frame R3: See figure
Frame R6: See figure
PT
on page 144.
RU
7. Secure the cables inside the drive with cable ties.
8. Frame R3: Leave the pair cable shields and grounding wires unconnected at the
SV
drive end, and ground them at the other cable end. Cut any unconnected wires at
the drive end. Frame R6 and R8: Ground the pair-cable shields and grounding
TR
wire under the clamp below the control unit.
ZH
9. Connect the conductors to the appropriate terminals of the control unit. See
Default IO connection diagram
10. Wire the optional modules if included in the delivery. See the option module user's
manual or installation guide.
Note:
• Leave the other ends of the control cable shields unconnected.
• Keep any signal wire pairs twisted as close to the terminals as possible.
and
...F
(R8)......on page 142.
...F (R6, R8)...
...G (R6)...
on page 144. Frame R8: See figure
on page 16.
2
, you must use a second
on page 143.
G (R3)...
...G (R3)...
on page 143.
...F
on page 143.
...G (R8)...

Werbung