Installation – Regulation sensor
3.10.1
In this submenu you must choose the sensor which will be used for
the regulation of the room managed by this unit.
To change the sensor, press on the desired option to frame in
green the button.
Ambient:
- The main zone programmer will regulate the temperature in the
room with this internal sensor.
Floor (ext):
(external sensor is needed 10k at 25°C)
- The external sensor is used as floor sensor to regulate the
temperature of the floor.
- The external sensor is used as deported ambient sensor to
regulate the temperature of the room.
Amb. + Limit 1
(external sensor is needed 10k at 25°C)
- The main zone programmer will regulate the temperature in the
room with the internal sensor the external sensor is used as floor
limiter.
Press a second time on the button to view the limitation settings.
High limit: 35°C (default value)
The floor will never overpass this value.
Low limit: 18.0°C (default value)
The floor will never decrease under this value.
28