Herunterladen Inhalt Inhalt Diese Seite drucken

Inhaltsverzeichnis; Safety Instructions; Symbols Used In This Document; Safety Advice For Handling Chlorine - Grundfos Vaccuperm VGB-103 Montage- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Vaccuperm VGB-103:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 36
English (GB) Installation and operating instructions
Original installation and operating instructions
CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
Warning
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.

1. Safety instructions

These installation and operating instructions contain important
information for the user of the product:
Technical data
Instructions for commissioning and use
Safety instructions
If you require further information, or if problems occur that are not
described in detail in this manual, please contact Grundfos.
4

1.1 Symbols used in this document

This manual contains the following standardised safety
instructions about possible residual risks:
Page
Warning
4
If these safety instructions are not observed, it may
4
result in personal injury.
4
4
If these safety instructions are not observed, it may
5
Caution
result in malfunction or damage to the equipment.
5
6
Notes or instructions that make the job easier and
Note
7
ensure safe operation.
7
7

1.2 Safety advice for handling chlorine

7
1.2.1 Hazards of chlorine gas
7
7
Warning
8
Toxic by inhalation.
8
Irritating to eyes, respiratory system and skin.
8
9
Causes whooping cough, dyspnoea and lacrimation.
9
Has a slight paralysing effect to the central nervous system.
9
Concentrations of more than 10 ppm chlorine gas in the
9
respiratory air mean an acute danger to life.
9
Inhaling air with a high concentration of chlorine gas for a long
10
time is lethal.
11
1.2.2 Hazards of liquid chlorine
11
11
Causes burns of skin.
12
Causes reddening and blistering of skin.
13
1.2.3 Rules of conduct
13
Change chlorine containers only with gas mask.
14
14
Enter contaminated rooms only with protective suit and
compressed-air respirator.
14
15
In case of flight wear gas mask, if possible. Observe wind
direction.
16
17

1.3 Protective equipment

17
17
1.3.1 Personal protective equipment
17
The operating authority of a chlorine gas dosing system has to
provide respiratory equipment (full-sight gas mask), personally
17
fitted, labelled by name, with an effective chlorine filter (B2P3)
18
and at least 1 spare filter per gas mask, for each operator. The
18
protective equipment must be stored easily accessible outside
the chlorine rooms.
19
For systems with chlorine drums at least 2 protective suits with
19
compressed-air respirators must be available.
1.3.2 Obligations of the operating authority
Introducing the operators to handling the protective
equipment.
The operators must use the personal protective equipment
regularly, or carry out exercises with it at least every 6 months.
The gas mask filters must be replaced regularly
- after the expiry of the date of durability
- at least 6 months after opening (note the opening date on
the filter)
- after contact with chlorine.
Observe employing prohibition according to the local laws.
1.3.3 Storage of the protective equipment
Outside the chlorine rooms
Well visible
Easily available at any time
Protected from dust and moisture.