 Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify
4
• For the [SET DATA] in Procedure
, select the SET
DATA of filter sign term from the following table.
SET DATA
Filter sign term
0000
None
0001
150 H
2500 H
0002
(Factory default)
0003
5000 H
0004
10000 H
 To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify
4
• For the set data in Procedure
, select the SET
DATA of shift value of detection temperature to be
set up from the following table.
SET DATA
Detection temperature shift value
0000
No shift
0001
+1°C
+2°C
0002
(Factory default)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
117-EN
 How to set up swing type
1. Push
for at least four seconds when the air
conditioner is not working.
flashes.
[F0]
Indicates CODE No.
.
[01]
.
2. Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit numbers
change as follows:
UNIT No.
UNIT No.
1-1
1-2
No
UNIT No.
display
1-4
The fan of the selected unit runs and the louvers
start swinging.
3. Select a swing type by pushing "TIME"
buttons.
Swing SET DATA
Swing SET DATA
Swing of louvers
Standard swing
0001
(Factory default)
[06]
.
0002
Dual swing
0003
Cycle swing
CAUTION
CAUTION
Do not set the swing SET DATA to "0000".
(This setting may cause a failure of the louvers.)
– 59 –
• About "Dual swing"
"Dual" means that louvers 01 and 03 are directed
and swing in one direction and louvers 02 and 04 are
directed and swing in the opposite direction.
(When louvers 01 and 03 are directed downward,
louvers 02 and 04 are directed horizontally.)
• About "Cycle swing"
The four louvers swing independently at respective
timings.
Indoor unit
UNIT No.
drain pipe
1-3
01
4. Push
button.
5. Push
button to complete the setting.
 How to set up louver lock
(No swing)
1. Push
four seconds when the air conditioner is not working.
flashes.
Indicates CODE No.
2. Select an indoor unit to be set by pushing
(left side of the button).
Each time you push the button, unit numbers
Indoor unit
change as follows:
refrigerant pipe
The fan of the selected unit runs and the louvers
start swinging.
04
UNIT No.
Electrical
control box
3. Select a louver you want to lock by pushing "TEMP."
03
4. Select the wind direction of the louver you do not
want to swing by pushing "TIME"
SET DATA
02
* When (4) or (5) is selected, dew drop may occur
during cooling mode.
5. Determine the setting by pushing
When the setting has been determined,
up.
6. Push
(right side of the button) for at least
[F1]
.
UNIT No.
UNIT No.
1-1
1-2
1-3
UNIT No.
1-4
buttons.
buttons.
(1)
(2)
(3)
0001
0002
0003
(4)
(5)
0004
0005
button.
lights
button to complete the setting.
0001-0005
(Louver lock position code)