REMOVAL OF COVER
REFITTING COVER
1
3
5.3. Leak checking and periodical inspections
A leak detection check must be carried out annually or as specified
by local regulations.
Use the appropriate equipment to empty or refill the cooling
installation (recovery machine, goggles, gloves, etc.)

5.4. Electrical checks

Systematically check the tightening of all screwed electrical
components.
Check regularly:
- Safety and control devices,
- The condition of electrical and refrigeration connections (e.g. for
any loosening or oxidation),
- Operating conditions,
- The mounting of the condensing unit on its base,
- The housing fixings (no vibration),
- Crankcase heater operation.
| Installation Instructions
5.5. Filter drier
Silensys® condensing units are all fitted with a brazed filter drier.
Replacement filter drier selection:
When changing the filter drier, ensure that it is replaced with an
equivalent in capacity and pressure drop and with the correct
direction of flow.
6- WARRANTY
For information concerning the condensing unit warranty, please
refer to our sales terms and conditions.

7- DECLARATION OF CONFORMITY

- We hereby declare that Silensys® condensing units comply with
the Low Voltage Directive 2006/95/CE.
- The applicable standards are:
- CEI 60335-I [EN 60 335-I ]: Safety of electrical domestic
equipment and similar – General description
- CEI 335-2-34 [EN 60 335-2-34]: Safety of electrical domestic
equipment and similar – Specific regulations for motor
compressors.
- CEI 60335-2-40 [EN 60 335-2-40 ]: Electrical and similar and
similar household appliances safety – Specific rules for electric
heat pumps, air-conditioners and dehumidifiers.
- When incorporating our products into a machine, the
Declaration of Incorporation of the manufacturer must be
observed. Our condensing units are not required to comply with
Pressure Equipment Directive 97/23/CE as they are classified as
a compatible sub-assembly.
- Certificates of conformity are available on our website
www.tecumseh.com and on request.
8- DECLARATION OF INCORPORATION
2
Only qualified staff are authorized to work on the condensing unit.
This product is defined as for installation in machines according to
European Directive 2006/42/CE. .
It is not permitted to run the condensing unit before the machine into
which it is incorporated has been declared in conformance with the
pertaining legislation. The condensing unit itself is therefore not
required to comply with Directive 2006/42/CE.
In its constant endeavor to improve its products, TECUMSEH EUROPE
S.A. reserves the right to change any information in this instruction
manual without prior notification.
Silensys® and L'Unite Hermétique® are registered trademarks of
TECUMSEH EUROPE S.A
366430 / 04.2013_b
11/40

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis