Herunterladen Inhalt Inhalt Diese Seite drucken

Declaration Of Conformity - Tecumseh WINTSYS Montageanleitung

Verflüssigungssätze mit wetterschutzgehäuse
Vorschau ausblenden Andere Handbücher für WINTSYS:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 10
Pre-start check list
1. The power supply voltage is compatible with that of the condensing unit.
2. Electrical safety devices are set correctly for the condensing unit.
3. Service valves are fully open.
4. The crankcase heater is working.
5. Condensing unit fan blades rotate freely.
6. The installation is given a final check for any possible faults.
Check list after start up
After the installation has been running for several hours, carry out
the following checks. Make sure that:
1. The voltage and current drawn by the condensing unit is correct.
2. The high and low operating pressures of the installation
are correct.
3. Fan blades are rotating freely.
4. Superheat and sub cooling.
5. The system is checked again for leaks.
Make sure that the installation is running smoothly.
Carry out a general inspection of the installation (e.g. cleanliness, vibration
and/or unusual noises). Ensure the settings and the functions of the
electrical circuits are correct
4.4 Fan speed control
The rotational speed of the fan has been optimised. Do not fit a pressure
sensing fan speed control or any other in series with the fan motor.
5 SERVICING AND MAINTENANCE
No unauthorized modifications to the condensing unit are allowed.
Authorization from Tecumseh must be obtained prior to any modification
whatsoever.
The housing can be cleaned with hot water (70°C). Do not use products
containing alcohol or ethanol.
Any faulty part must be replaced with an original spare part.
In order to maintain the low noise levels of the condensing unit over time,
we recommend replacing the anti-vibration mounts as soon as any change
in the noise or vibration level of the unit is noticed.
Access to the connections, fan and compressor compartments can be
gained by either raising the housing and securing it with the strut provided
or, withdrawing the hinge pins and removing the housing.
5.1 Fan
Housing size1 & 2
Housing size 3
Installation instructions
5.2 Condenser
The condenser and the condensing unit should be cleaned at least once
a year. Access from the inside of the unit can be gained by removing
the fan cover.
5.3 Leak checking and periodical inspections
A leak detection check must be carried out annually or as specified by local
regulations.
Check regularly:
5.4 Electrical checks
Systematically check all electrical components with screwed terminals.
Tighten any connections if necessary.
Check regularly:
5.5 Filter drier
Housed condensing units are fitted with a brazed filter drier.
Replacement filter drier selection:
When changing the filter drier, ensure that it is replaced with an equivalent
in capacity and pressure drop and with the correct direction of flow.
6 WARRANTY
For information concerning the condensing unit warranty, please refer to
our sales terms and conditions.
7 DECLARATION OF CONFORMITY
-
-
See appendix 5, page 27.
8 DECLARATION OF INCORPORATION
Only qualified staff are authorized to work on the condensing unit.
This product is defined as for installation in machines according to European
Directive 2006/42/CE.
It is not permitted to run the condensing unit before the machine into which
it is incorporated has been declared in conformance with the pertaining
legislation. The condensing unit itself is therefore not required to comply
with Directive 2006/42/CE.
In its constant endeavour to improve its products, TECUMSEH EUROPE
S.A. reserves the right to change any information in this instruction manual
without prior notification.
the condition of refrigeration connections (e.g. for any loosening
or oxidation).
operating conditions.
the mounting of the condensing unit on its base.
the housing fixings (no vibration).
safety and control devices,
crankcase heater operation.
We hereby declare that housed condensing units comply with the
Low Voltage Directive 2006/95/CE.
The applicable standards are:
CEI 335-I [ EN 60 335-I ]: Safety of electrical domestic equipment and
similar - General description
CEI 335-2-34 [ EN 60 335-2-34 ]: Safety of electrical domestic
equipment and similar – Specific regulations for motor compressors.
To incorporate our products into a machine, the Declaration of
Incorporation of the manufacturer must be observed. Our condensing
units are not required to comply with Pressure Equipment Directive
97/23/CE as they are classified as a compatible sub-assembly.
Certificates of conformity are available on request.
366 395 / 03.2010
9/40

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis