EBV 200 is a load monitor used to disconnect output
that exceeds the output set on the load monitor. EBV
200 consists of the Load Monitor 100 module, plate,
cable set and three current transformers.
5 V
Function
When many power consumers are connected in the
property at the same time as the immersion heater is
operating, there is a risk of the property's main fuse
tripping.
If the phase current becomes so high, the load moni-
tor reduces the output of the immersion heater until
there is no longer a risk of the main fuses tripping.
When the general power consumption drops suffi-
ciently, the immersion heater is connected again.
A fixed green light indicates that the output is less
than the main fuse's nominal current, which means no
limitation.
A fixed red light indicates that the output is stepped
down by approximately 10 s step time.
During the period the red LED flashes the output has
dropped below the main fuse's nominal current. The
cutout of supply will continue for 10 minutes.
Elanslutning
GB
The current control "Ström" is set to the value of the
main fuse. When the current output exceeds this val-
ue, the load monitor starts to step down the output of
the immersion heater.
With the current control "Marginal" the difference is
chosen between the main fuse's nominal current and
that current which allows the power to be cut in again.
For the 6 kW immersion heater, Marginal is set to 5 A.
For 9 kW, Marginal is set to 4.5 A. The value should
always be set to the current that the greatest discon-
nected load could draw.
Current setting
Current margin
Supply voltage
EBV 200
Setting the limitation

Technical specifications

16 - 35 A
2 - 10 A
230 V/50 Hz