Technical Data
Terminal wire area
Tightening torque
Current
I
- base
b
I
- rated
n
I
- reference
ref
- maximum
I
max
I
- minimum
min
Frequency
Accuracy
Material
Weight
Operating temp.
Storage temp.
Humidity
Resistance to heat
Outputs
Direct conn.
1 - 25 mm²
2.0 Nm
5 A
5 A
65 A
0.25 A
50 or 60 Hz ± 5%
1%, 2%
Polycarbonate in transparent front glass.
Glass reinforced polycarbonate in bottom
case and upper case. Polycarbonate in ter-
minal cover.
-40 °C to +70 °C
-40 °C to +85 °C
75% yearly average, 95% on 30 days/year
Terminal 960°C, cover 650°C (IEC 60695-
2-1)
5
EN
Indirect conn.
0.5 - 10 mm²
1.5 Nm
1 A
1 A
6 A
0.01 A
0.5%, 1%