Frames r4 and r5
Vorschau ausblenden Andere Handbücher für ACS880-01:
Inhaltsverzeichnis

Werbung

.
A
A = TN-S system, B1 = Corner-grounded system, B2 = Midpoint-grounded system, C = IT system
WARNING! Do not install the drive with EMC filter options +E200 and +E202
connected to a system that the filter is not suitable for. This can cause danger,
or damage the drive.
WARNING! Do not install the drive with the ground-to-phase varistor
connected to a system that the varistor is not suitable for. If you do, the varistor
circuit can be damaged. See the drive hardware manual.
Note: With option +E201, remove EMC AC, EMC DC and VAR screws in for systems
other than TN-S if not removed at the factory. For more information, contact ABB.
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before you
connect it to the drive.
Check the insulation of the motor cable and motor when the cable is disconnected
from the drive, see figure
each phase conductor and the Protective Earth conductor using a measuring voltage
of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm
(reference value at 25 °C or 77 °F). For the insulation resistance of other motors,
B1
L1
L2
L3
N
PE
B2
G
on page 99. Measure the insulation resistance between
EN – Quick installation guide 5
C
L1
L2
L3
PE
L1
L2
L3
PE
L1
L2
L3