Herunterladen Inhalt Inhalt Diese Seite drucken

Warnings For Knx/Eib Installations - Gewiss Chorus GW 10 761 Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

INST LL TION INSTRUCTIONS
Mounting on a 2-place box

Warnings for KNX/EIB installations

1. The length of the bus line between the Easy timer-thermostat and the power supply
unit must not exceed 350 metres.
2. The length of the bus line between the Easy timer-thermostat and the most distant
KNX/EIB device must not exceed 700 metres.
3. If possible do not create ring circuits so as to prevent undesirable signals and
overloads.
4. Keep a distance of at least 4 mm between the individually insulated cables of the bus
line and those of the electric line.
Bus
5. Do not damage the electrical continuity conductor of the shielding.
Shield
64
U P
230 V
≥ 4 mm
Bus cable
Electrical continuity
conductor

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Chorus gw 14 761

Inhaltsverzeichnis