Herunterladen Inhalt Inhalt Diese Seite drucken

Hach SC1500 Bedienungsanleitung Seite 16

Vorschau ausblenden Andere Handbücher für SC1500:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 23
Table 5 Wiring information—analog outputs (continued)
Terminal
Description
4
Output 2–
5
Output 3+
Connect the analog/digital inputs
Electrocution hazard. Always remove power to the instrument before making electrical connections.
If the instrument has the optional input card, the instrument has four 4–20 mA inputs. Such inputs are
commonly used for looping in external devices' analog or digital signals.
Connect each external device to an input as necessary. Refer to
the mobile application to configure each of the inputs to agree with a measured parameter (e.g. flow).
Make connections with twisted-pair shielded wire and connect the shield to the shield terminal.
• Do not connect the shield at both ends of the cable.
• Use of non-shielded cable may result in radio frequency emission or susceptibility levels higher
than allowed.
Notes:
• The input terminals accept 15 to 26 AWG wire.
• The inputs are isolated from the other electronics, but are not isolated from each other.
Figure 9 Connect the inputs
1 Wiring information—inputs
2 Input card
For wiring information, refer to the SC1000 user manual, section 3.6.2 Input Card Connections.
Install the Profibus DP card
Refer to the applicable probe manual for operating instructions and instrument profiles. Refer to the
company web site for the latest GSD files and documentation.
To connect the Profibus DP card to the SC controller, refer to the SC controller Profibus
DP/V1 network card documentation. Install the Profibus card. Refer to
16 English
Terminal
Description
9
Shield (connected to protective earth)
D A N G E R
3 Input terminal
Figure 9
to connect the inputs. Use
Figure 10
and
Table
6.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis