Appendix
A.1 I/O Connections and Wiring
Terminal Block Wiring - 7ME39400SA00 - Analog Input Module - Single Channel
(Refer to manual drawing 1010N-5S2-7)
These connection diagrams apply to the part numbers listed below.
Table A- 20
FUS1010
FUH1010
Figure A-6
Table A- 21
Pin
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
70
Connection Diagrams and Part Numbers
7ME3530, 7ME3533
7ME3600, 7ME3603
7ME39400SA00 - Analog Input Module
Input/Output Wiring TB1 7ME39400SA00 - Analog Input Module
Color
Function
Black
RTD Current High
White
RTD Voltage High
Green
RTD Voltage Low
Red
RTD Current Low
Blue
Ground
1010N-5S2-7 Drawing
Description
RTD Temperature measurement T1 or
Channel 1 Ts (Supply Temperature)
FUS1010 IP65 NEMA 4X & IP66 NEMA 7 Quick Start
Operating Instructions, 07/2014, A5E03086486-AD
Wiring/Cable
AWG. 14 - 24 /
1000 Ft max w/o
factory approval