Standard configuration with extensions: top mounting
• Designed for top mounting, for high or low level alarm. Suspend the probe vertically so
that it reaches into the process at the desired detection level.
Process Cautions
• The maximum allowable torque on a horizontally installed rod is 15 Nm.
• Keep unit out of path of falling material, or protect probe from falling material.
• Avoid areas where material build up occurs.
• Take into account material surface configuration when installing unit.
• Ensure tensile load does not exceed probe or vessel ratings

Mounting Instructions

Pointek CLS200/300 is available in three thread types: NPT, or BSPT (R), and BSPP (G)
sure the mounting connection threads are of the same type, then simply screw the device into
the process connection, and hand tighten.
Wiring
WARNING: All field wiring must have insulation suitable for at least
250 V.
Notes:
Only qualified personnel are authorized to install and operate this equipment in
accordance with established safety practices and standards.
The Protective Earth Terminal indicated by
ground.
All wiring must be done by qualified personnel in accordance with all governing
regulations.
The equipment must be protected by a 15A fuse or circuit breaker in the building
installation.
A circuit breaker or switch in the building installation, marked as a disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
Use shielded twisted pair cable, wire gauge 20 AWG to 14 AWG (0.5 mm
2
2.0 mm
).
Maximum working voltage between adjacent relay contacts is 250 V.
Relay contact terminals are for use with equipment which has no accessible live
parts and wiring which has insulation suitable for at least 250 V.
1.
A
sanitary connection is also available.
7ML19985QY81
Pointek CLS200/300 (Standard) – QUICK START MANUAL
must be connected to reliable
50 mm
(2") min
1
. Make
2
to
Page EN-5