10-6. Address setting

・Set the address setting switch as follows.
Indoor unit (Main, Sub)
Outdoor unit (OC)
Main
HBC controller
Sub
Main
ME remote controller
Sub
MA remote controller
* Make indoor unit group settings from remote controllers after turning on the power to all units.
WT08842X01
Assign the lowest address to the main indoor unit in the group, and assign sequential
addresses to the rest of the indoor units in the same group.
* In a system with a sub HBC controller, make the settings for the indoor units in the
following order. (Set the addresses so that the addresses of ① are smaller than those of
②.)
Indoor units that are connected to the main HBC controller
Indoor units that are connected to the sub HBC controller
Assign sequential addresses to the outdoor units in the same refrigerant system.
* To set the address to 100, the address setting switch must be set to 50.
Assign an address that equals the address of the outdoor unit plus 1. If the address that
is assigned to the main HBC controller overlaps any of the addresses that are assigned
to the outdoor units or to the sub HBC controller, use a different, unused address within
the setting range.
* To set the address to 100, the address setting switch must be set to 50.
Assign an address that equals the lowest address of the indoor units that are connected
to the sub HBC controller plus 50.
* To set the address to 100, the address setting switch must be set to 50.
Assign an address that equals the address of the main indoor unit in the group plus 100.
Assign an address that equals the address of the main indoor unit in the group plus 150.
Address setting is not required. (The Main/Sub setting is required.)
GB-49
Address setting method
Address
01 to 50
51 to 100
51 to 100
51 to 100
101 to 150
151 to 200
Address setting switch (Outdoor units)