Herunterladen Inhalt Inhalt Diese Seite drucken

Mitsubishi Electric CITY MULTI PURY-WP200YJM-A Installationshandbuch Seite 25

Vorschau ausblenden Andere Handbücher für CITY MULTI PURY-WP200YJM-A:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 59
((E)M300)
A
1
H
H'
h
1
<A>, <B> Main HBC controller (Total capacity of indoor units: WP375 or below)
<C> Sub HBC controller (Total capacity of indoor units <B> + <C>: WP375 or below)
Outdoor unit
Indoor unit
Main HBC controller
Sub HBC controller
2-Branch Joint Pipe (not supplied)
Joint Pipe Kit (not supplied)
Max. 3 sets for 1 port (Total capacity ≤ WP80)
Between outdoor unit and HBC controller (refrigerant pipework)
Pipe length
Water pipework between indoor units and HBC controller
Between HBC controllers
Between HBC controller and outdoor
units
Difference of
Between indoor units and HBC controller
elevation
Between indoor units
Between HBC controllers
*1 The values marked with *1 indicate the values when the total indoor unit capacity exceeds 130% of outdoor unit capacity.
WT08842X01
CMB-WM108V-AA + CMB-WM108V-AB
(CMB-WM1016V-AA) (CMB-WM1016V-AB)
<A>
A
2
B
A
3
<B>
a
b
(WP10-WP80)
(WP100, WP125)
Item
Outdoor unit above HBC
controller
Outdoor unit below HBC
controller
GB-23
h
g
3
<C>
f
b'
e
c
d
Piping portion
A
+ A
1
2
f + g
B
H
H'
h
1
h
2
h
3
h
1
h
2
Allowable value
+ A
110 m (360 ft) or below
3
60 m (196 ft) or below
40 m (131 ft) or below
50 m (164 ft) or below
40 m (131 ft) or below
15 m (10 m
)
*1
(49 ft (32 ft
)) or below
*1
15 m (10 m
)
*1
(49 ft (32 ft
)) or below
*1
15 m (10 m
)
*1
(49 ft (32 ft
)) or below
*1

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis