Herunterladen Inhalt Inhalt Diese Seite drucken

Thermal Insulation For Pipes - Mitsubishi Electric CITY MULTI PURY-WP200YJM-A Installationshandbuch

Vorschau ausblenden Andere Handbücher für CITY MULTI PURY-WP200YJM-A:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 59

9-7. Thermal insulation for pipes

Insulate pipes to prevent condensation.
- Condensation may collect and drip from the unit onto the ceiling or floor.
Insulate the high- and low-pressure pipes, and liquid and gas pipes separately with polyethylene foam insulation
materials. Inadequate insulation may cause condensation to drip. Pipes in the ceiling are especially vulnerable to
condensation and require adequate insulation.
9-7-1. Insulation material
・Check that the insulation materials meet the standards in the table below.
Between an outdoor unit and HBC controller
Thickness [mm (in)]
Heat resistance
Between an HBC controller and indoor unit
Refer to the HBC controller Installation Manual for details.
Glass fiber + Steel wire
Insulation
material A
Adhesive + Heat-resistant polyethylene foam + Adhesive tape
Indoor
Outer
Under the floor and exposed
covering B
Outdoor
* If a polyethylene cover is used as an outer covering, asphalt roofing is not necessary.
・Do not insulate the electric wires.
WT08842X01
High-pressure pipe
Min. 10 (7/16)
Min. 120°C (248°F)
Steel wire
Pipe
Oily mastic asphalt or asphalt
Insulation material A
Outer covering B
Vinyl tape
Waterproof hemp cloth + Bronze asphalt
Waterproof hemp cloth + Zinc plate + Oily paint
High-pressure pipe or liquid pipe
Low-pressure pipe or gas pipe
Electric wire
Finishing tape
Insulation material
Low-pressure pipe
Min. 20 (13/16)
GB-31