Herunterladen Inhalt Inhalt Diese Seite drucken

Specification; Checking The Earth Conductor; Dimensions And Connections - STIEBEL ELTRON DHM 3 Bedienung Und Installation

Vorschau ausblenden Andere Handbücher für DHM 3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
INsTALLATIoN

Specification

14.3 Checking the earth conductor

f Check the earth conductor (in Germany e.g. DGUV A3) on the
f
earth conductor contact of the power cable and on the appli-
ance connector.
14.4 Tests in accordance with VDE 0701/0702
Earth conductor check
f Check the earth conductor (in Germany e.g. BGV A3) on the
f
earth conductor contact of the power cable and on the appli-
ance connector.
Insulation resistance
f If an appliance with a rated heating output of > 3.5 kW does
f
not achieve an insulation resistance of 300 kΩ, we recom-
mend that the insulating properties of the appliance are
checked by conducting a differential current test of the earth
conductor current / leakage current to VDE 0701/0702 (Fig.
C.3b).
14.5 Replacing the power cable for the DHM 6
f If replacing the cable for the DHM 6, use a power cable with
f
4 mm² cross-section
www.stiebel-eltron.com
15. Specification

15.1 Dimensions and connections

c01
c06
30
120
190
b02 Entry electrical cables I
b03 Entry electrical cables II
c01
Cold water inlet
c06
DHW outlet
20
b02
b03
82
DHM
Male thread
G 3/8 A
Male thread
G 3/8 A
DHM |
41

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Dhm 4Dhm 6Dhm 7

Inhaltsverzeichnis