6. Commissioning / 7. Analogue output signal
Commissioning
During the commissioning process pressure surges must be avoided
at all costs
Install the pressure connection according to the symbols
high pressure
Use the pressure gauge only if the diaphragm is undamaged and if it
is in perfect condition with regard to safety

7. Analogue output signal (air2guide P+E)

Output signal
Power supply U
Measuring accuracy sensor ±3 % of full scale value
Electrical connection

Terminal configuration

Output signal 4 ... 20 mA, 2-wire
Output signal 0 ... 10 V, 3-wire
WIKA operating instructions air2guide models A2G-10, A2G-15
low pressure
4 ... 20 mA, 2-wire or
0 ... 10 V, 3-wire
4 ... 20 mA, 2-wire: DC 14 ... 35 V
B
0 ... 10 V, 3-wire: DC 15 ... 35 V
M12 cable connection with screw
terminals
Power supply
DC 14 ... 35 V
Power supply
DC 15 ... 35 V