SW 2 – RS–485 serial settings:
• SW 2.1 – data signaling rate
– ON: 9600 bps
– OFF: 19200 bps (factory default)
• SW 2.2 – manufacturer's use only: must be left in the 'on' position (factory default)
• SW 2.3 – parity bit
– ON: EVEN (factory default)
– OFF: NONE
• SW 2.4 – reserved for future use: must be left in the 'off' position (factory default)
NOTICE
All the devices belonging to one RS–485 bus must have the same serial
settings and the Modbus device address of each Transclinic cannot be used
more than once.
NOTICE
After modifying any DIP switch setting, the changes need to be applied by
powering off and then back on the equipment.
NOTICE
Regardless of the SW 2.3 parity bit setting there is always ONE stop bit.
63