3.6 DIP switch configuration

Use the DIP switches to configure the Modbus device address (SW 1) and the RS–485
serial settings (SW 2). The photo shows the factory default settings.
SW1 – The following table specifies the binary coding of the Modbus device address
via DIP switches. The factory default slave address is 1 (i.e. SW 1.1 in the 'on' position
and SW 1.2 to SW 1.8 in the 'off' position). As an example the DIP switch coding for
Modbus address 175 is shown (10101111 in binary).
Weight
Address
increment
Example address 175
62
SW 1.1
SW 1.2
2
(LSB)
2
0
1
1
2
ON
ON
SW 1.3
SW 1.4
2
2
2
3
4
8
ON
ON
SW 1.5
SW 1.6
2
2
4
5
16
32
OFF
ON
SW 1.7
SW 1.8
2
2
(MSB)
6
7
64
128
OFF
ON