7.7.1 Alarm Output "AL OUT (-)" (2)
Reaction Mode
You can trigger the "AL OUT (-)" (2) alarm output in different ways. For this purpose, this code
lock offers you convenient options to specify the activation mode.
To set the required activation mode, enter the following combination:
MMMM MMMM * 55 C #
C in this case stands for the desired mode type.
Explanation of the various modes:
C = 0
no function
C = 1
allows the triggering of the alarm output "AL OUT (-)" (2) in connection with the
extended door monitoring (also see chapter 7.6.2)
C = 2
enables triggering of the "AL OUT (-)" (2) alarm output via the sabotage contact.
C = 3
enables modes 1 and 2 jointly.

7.8 Restore Factory Settings (RESET)

When performing a reset, all settings made previously are reset.
• Remove your code lock from the power supply.
• Move the "System Restore" (7) jumper
to the position indicated on the right.
• Reconnect the operating voltage again.
• The internal signaller is now active.
• Move the "System Restore" (7) jumper
to the position indicated on the right.