Combustion head settings indicated in the schedule are valid for most cases.
The setting of the fan output according to the installation should normally be done only through
the air damper. Should one subsequently want to retouch also the setting of the combustion head,
with the burner running, operate on the rod (1) with a 6 mm spanner (2) as follows:
2
1
6
4
AIR DAMPER ADJUSTMENT :
A
D
It is important to take account of the fact that the air output of the fan differs according to
whether the burner has its metal cover fitted or not.
Therefore we recommended to proceed as follows:
– adjust the air damper as indicated in the schedule (4, page 5);
– mount the cover, simply by means of the upper screw;
– check smoke number;
– should it become necessary to modify the air output, remove the cover by loosening the screw,
adjust the air damper, remount the cover and finally recheck the smoke number.
2341
Turn to the right: (sign
volume of air entering the combustion chamber and
3
thus diminishing its pressure.
There is a reduction of CO
flame to the air diffuser disc improves.
(Setting advisable for ignitions at low temperatures).
Turn to the left: (sign
ume of air entering the combustion chamber and thus
increasing its pressure. The CO
adhesion of the flame to the diffuser tends to reduce.
(This setting is not advisable for ignitions at low tem-
peratures).
In any case do not bring the combustion head setting
more than one point away from that indicated in the
D5323
schedule. One set-point corresponds to 3 turns of the
rod; a hole (3) at its end facilitates counting the number
of turns.
The mobile air damper (A) operated by the jack (B) as-
sures the complete opening of the air intake.
The regulation of the air-rate is made by adjusting the
B
fixed air damper (C), after loosing the screws (D).
When the optimal regulation is reached, screw tight
the screws (D) to assure a free movement of the mo-
bile air damper (A).
C
The settings indicated in the schedule refer to the burn-
er with its metal cover fitted and the combustion cham-
ber with "zero" depression.
These regulations are purely indicative.
Each installation however, has its own unpredictable
D
working conditions: actual nozzle output; positive or
negative pressure in the combustion-chamber, the
need of excess air, etc.
All these conditions may require a different air-damper
D5786
setting.
– ), in order to reduce the vol-
6
GB
+
), in order to increase the
and the adhesion of the
2
improves and the
2