Herunterladen Inhalt Inhalt Diese Seite drucken

Combustion Adjustment - Riello Burners Riello 40 Montage- Und Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler,
adjustment and testing must be carried out observing the instruction manual of the boiler, includ-
ing verification of the CO and CO
average temperature of the water in the boiler.
To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of
the combustion head and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO
Nozzle
1
GPH
Angle
0.40
80°
0.50
60° / 80°
0.60
60° / 80°
0.65
60° / 80°
0.75
60°
1
NOZZLES RECOMMENDED: Monarch type R - NS; Delavan type W - A - E
Angle :
2
PRESSURE
3
COMBUSTION HEAD SETTING : This is done when fitting the nozzle, with the blast tube
Terminal plane of the blast tube
D5322
Blast tube
2341
concentration in the flue gases, their temperatures and the
2
at sea level and with light oil and room temperature of 20
2
Pump pressure
Burner output
2
bar
12
12
12
12
12
Steinen type H - Q
in most cases.
60° :
in case of flame detachment, during ignitions at low tem-
80° :
peratures.
the pump leaves the factory set at this value
12 bar :
14 bar : improves flame retention; it is therefore suitable for ignitions
at low temperatures.
removed. It depends on the output of the burner and is
carried out by rotating the regulating rod, till the terminal
plane of the blast tube is level with the set-point, as indi-
cated in the schedule.
2
5
3
1
Regulating rod
Shutter
Comb. head
adjustment
kg/h ± 4%
Set-point
1.6
2.0
2.4
2.6
3.0
;
Danfoss type H - B
In the sketch on the left, the combus-
tion head is set for an output of 0.60
GPH at 12 bar, while the shutter is
level with set-point 2, as required by
the above schedule.
5
GB
°C.
Air damper
adjustment
3
4
Set-point
0
2.4
1
3.1
2
3.6
3
3.8
4
4.0

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

G3431t1

Inhaltsverzeichnis