Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Riello Burners Riello 40 Montage Und Bedienungs Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3

TECHNICAL DATA

TYPE
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC - 2004/108/EC,
Low Voltage 73/23/EEC - 2006/95/EC, Machines 98/37/EEC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529.
Parts Available from
www.sparesgiant.com
8
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
7 – Hydraulic jack with air-damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Combustion head adjustment screw
2346
445T1
28 – 60 kW
Light oil, max. viscosity at 20 °C: 6 mm
Single phase,
230 V
Run current 0.75 A – 2850 rpm – 298 rad/s
4 μF
Secondary 8 kV – 16 mA
Pressure 7 – 15 bar
0.130 kW
Fig. 1
7
6
6
9
D8067
EQUIPMENT
Quantity
2
1
4
1
1
1
1
GB
2.3 – 5 kg/h
2
/s
~
± 10%
50Hz
2
Description
Flexible oil pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
to be fixed to boiler
Maintenance assembly
Screw and nuts for flange
Grommet
ENGLISH
10
1
5

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

445t1G5

Inhaltsverzeichnis