Figure 7
Current transformer connection
As single wires, solid conductors as well as stranded conductors with con-
ductor sleeves can be used. Up to two single wires with identical cross-
sections can be used per connection.
Alternatively, short circuit links (Order no. C53207-A406-D193-1) can be
used for vertically arranged terminal points. If short circuit links are used,
only ring lugs are permitted.
When connecting single wires, the following cross-sections are allowed::
Wire cross-section:
Conductor sleeve with plastic sleeve
Stripping length:
(when used without conductor sleeve)
Mechanical Requirements
The fixing elements and the connected components are designed for the
following mechanical requirements:
Permissible tightening torque at the terminal
screw
Permissible traction per connected conduc-
tor
16
AWG 14-10
2
(2.0 mm
to 5.2 mm
L = 10 mm (0.39 in) or
L = 12 mm (0.47 in)
15 mm (0.59 in)
Only solid copper wires
may be used.
2.7 Nm (23.9 lb.in.)
With solid conductors the
allowed maximum tighte-
ning torque is 2 Nm.
80 N based on IEC 60947-
1 (VDE 660, Part 100)
SIPROTEC 7SJ80 / 7SK80 V4.60, Product Information
E50417-K1150-C342-A6, Edition 07.2010
2
)