Troubleshooting
LED
Alarm
Lighting*
Grid consumption
Orange, 1
Low pow. PV conn.
Orange, 1
Power supply fault
Red, 1
Idc grid injection
Red, 3
Config. change
Red, 1
Isolation alarm
Orange, 5
Satur. alarm Iac
Orange, 5
Low Vdc
Orange, 1
Electric arc detection
Not applicable Not applicable
* The number of flashes is indicated.
Warnings
LED
Alarm
Lighting*
Blocked fan
Orange, 7
High temperature
Orange, 7
Low temperature
Orange, 7
High Vdc
Orange, 7
Orange, 7 Not
String kit comm.
applicable
Self-cons. commun.
Orange, 7
Surge arrester error
Orange, 7
* The number of flashes is indicated.
ABO2011IQM01_A - Installation and Operation Manual
Description
Grid consumption power out of the
permitted range
The generated power in the PV
array is not sufficient to connect to
the AC grid
Fault in power supply to the
electronic circuit boards
DC current fed to the grid out of
the permitted range
Inverter setting change
Insulation resistance out of range
AC current saturation
Low DC voltage
Description
Possible fan blockage
Power regulation due to
temperature above operating
temperature
Temperature below operating
temperature
High DC input voltage
Communication failure with strings
reading card (only in versions P
and P+)No applicable
Communication fault with the self
consumption devices (wattmeter
or INGECON EMS Manager)
Fault in DC arresters
Solution
This may be due to a low irradiance level. Otherwise,
check the PV array.
Check the correct connection of the DC cables.
Open the unit and check the correct connection of
the control board.
Check the installation in the AC part.
If the error persists, contact the Technical Service.
Normal shut down due to a change in the inverter
setting.
Check, on the display, that the PV array grounding is
correctly configured. Search for an insulation fault in
the PV array. If one of the poles is grounded, check
the grounding fuse.
Check the installation in the AC part.
If the error persists, contact the Technical Service.
This may be due to a low irradiance level. Otherwise,
check the PV array.
Not applicable
Solution
Check the condition of the fan and that there are no
elements that prevent it functioning properly.
Check the room temperature does not exceed the
specified maximum temperature and the inverter
is not exposed to direct sunlight. Also check the
functioning of the fans.
Check the room temperature is not below the
specified minimum temperature.
Check the connections of the PV array, ensuring the
series-parallel configuration of the panels is correct,
and that the maximum voltage of the MPP has not
been exceeded.
Contact technical service.
Check the connection of the different elements. If
the error persists, contact the Technical Service.
Check the condition of the surge arresters and
replace as required.