5.4 Installation of safety group
Connect the safety group included in the delivery
to the right hand side ball valve connection at the
primary circuit.
5.5 Installation of expansion tank
ATTENTION!
Too high continuous temperatures
and steam shocks may lead to
damage to property!
For this reason:
– Only use a correctly dimensioned
diaphragm expansion tank which is
suitable for the application range and
the heat transfer medium.
– Mount expansion tank at a lower
level than the safety group.
– If the expansion tank has to be instal-
led at the same or a higher level than
the safety group, always install a
thermal insulation loop.
– The expansion tank must always be
installed with the connection poin-
ting upwards.
1.
Mount and connect expansion tank, see docu-
mentation of expansion tank supplier.
Illustr. 21: Installation of safety group
Illustr. 22: Installation of expansion tank
Installation